ES-8123 Rev.19

MDP-SP

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
LOW FREQUENCY USE

Functions & Features
• Designed specifically to protect frequency generating devices such like flowmeters and frequency transmitters from lightning surge damage that enters on the wiring between these instruments
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging the protector element

MODEL: MDP–SP[1]

ORDERING INFORMATION

• Code number: MDP-SP[1]
Specify a code from below for [1].
  (e.g. MDP-SP/A33/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 140 g (0.31 lb), standard
165 g (0.36 lb), with DIN rail mounting adapter

PERFORMANCE

Max. continuous operating voltage (Uc): 
 B to C: ±14 V 
 B or C to A: 14 V 
 Line to earth: ±140 V
Voltage protection level (Up):
• @ 1 kV (100 A)
 2 to 3: ±30 V  
 2 or 3 to 1: 30 V 
 Line to earth: ±650 V
• @ 2 kV (1 kA) 
 2 to 3: ±30 V  
 2 or 3 to 1: 30 V 
 Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
 B to C: ≤ 10 μA @ ±14 V DC
 B or C to A: ≤ 10 μA @ 14 V DC
 Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
Nominal current (IN): 50 mA
Internal series resistance: 10 Ω ±10 %
Capacitance @ 1 MHz:
 Line to line:  ≤ 1000 pF
 Line to earth: ≤ 100 pF
Surge protection: IEC 61643-21 Categories C1, C2, D1

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

CONNECTION EXAMPLES

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM