ES-8106 Rev.7
MDR2
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
MULTI-CHANNEL USE
(high discharge current capacity)
Functions & Features
• Protection for semiconductor switches of discrete outputs against lightning surge damage
• Applicable to both negative and positive common signals
• Applicable to multi analog signals (non-isolation between channels)
• Space saving with multi-channel protectors
• LED monitor indicating degradation of voltage limiter
• LED monitor driven by discrete I/O signal without auxiliary power supply
MODEL: MDR2–8[1][2]
ORDERING INFORMATION
• Code number: MDR2-8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. MDR2-8NA)
NUMBER OF PROTECTORS
8
: 8 points
[1] COMMON
N
: Negative common (NPN)
P
: Positive common (PNP)
[2] LEAKAGE CURRENT INDICATOR
Y
: None
A
: With
GENERAL SPECIFICATIONS
Construction
: terminal board; terminal cover provided
Connection
: M3.5 screw terminals (torque 1.1 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Steel
LED monitor
: Red
The leakage current from voltage limiter increases due to its degradation.
LED becomes brighter gradually in proportion to this leakage current.
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface
Weight
: 520 g (1.15 lb)
PERFORMANCE
Response time
: ≤ 4 nsec
Leakage current @ max. voltage
Line to COM: 5 μA
Line to line: 5 μA
COM to earth: 5 μA
Max. discharge current (Imax)
Line to COM: 10 kA
Line to line: 10 kA
COM to earth: 10 kA
Nominal current (I
N
)
: 150 mA
Internal series resistance
: 22 Ω ±20 %
Surge protection
: IEC 61643-21 Categories C1, C2, D1
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY