ES-8220 Rev.6
MDW5-CC
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR CC-Link
Functions & Features
• For CC-Link communication
• Designed specifically for the network
• Available with CC-Link Ver.1.10/2.00
• DIN rail mounting
MODEL: MDW5–CC
ORDERING INFORMATION
• Code number: MDW5-CC
APPLICABLE NETWORK
CC-Link Ver.1.10/2.00
GENERAL SPECIFICATIONS
Construction
: Terminal block
Connection
Surge side
: M3.5 screw terminals (torque 0.8 N·m)
Protected device side
: M3 screw terminals
(torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 100 g (0.22 lb)
PERFORMANCE
Max. continuous operating voltage
(Uc)
:
Line to line (DA - DB): ±5 V
Line to earth (DA or DB - DG): ±5 V
Line to shield or earth (DG - SLD or FG): ±50 V
Voltage protection level (Up)
:
@ 4 kV (1.2/50 μsec.)
Line to line (DA-DB): ±20 V
Line to earth (DA or DB to DG): +20 V, -10 V
Line to shield or earth (DG - SLD or FG): ±300 V
Response time
:
Line to line (DA-DB): ≤ 4 nsec.
Line to line (DA or DB - DG): ≤ 4 nsec.
Line or shield to earth (DG - SLD or FG): ≤ 20 nsec.
Leakage current
(@ max. continuous operating voltage)
Line to line (DA - DB): 0.2 mA
Line to line (DA or DB to DG): 0.2 mA
Line to shield or earth (DG to SLD or FG): 1 mA
Maximum discharge current:
10 kA (8/20 μsec.)
Max. load current
: 100 mA
Internal series resistance
: Approx. 2 Ω (per wire)
Capacitance @ 1 MHz
:
Line to line (DA to DB): approx. 30 pF
Line to Line (DA or DB to DG): approx. 60 pF
Line to earth (DG to SLD or FG): approx. 1000 pF
Surge protection
: IEC 61643-21 Categories C1, C2, D1
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMS EN 61000-6-2
RoHS Directive
CONNECTION EXAMPLES
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY