ES-8271 Rev.5
MGA-100
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR
FOR POWER SUPPLY USE
(2 A, 120 V AC / 170 V DC; rack-mounted)
Functions & Features
• Designed specifically for AC/DC power supplies up to
2 amps
• Rack-mounted
• Two channels in one housing
MODEL: MGA–100
ORDERING INFORMATION
• Code number: MGA-100
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals at the front; terminal cover provided
Connection
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Monitor lamp
: Red LED turns on when the power is supplied.
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Rack-mounted; Standard Rack Mounting Frame BX-16G available
Weight
: 200 g (0.44 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 190 V min.
Line to ground: 410 V min.
Maximum surge voltage
Line to line: 400 V max.
Line to ground: 800 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time
: ≤ 0.1 μsec.
Leakage current
Line to line: ≤ 2 mA at 150 V DC
Line to ground: ≤ 1 mA at 300 V DC
Max. discharge current (Imax)
: 1000 A (8/ 20 μsec.)
Max. load current
: 2 A
Rated line voltage
: 120 V AC, 170 V DC
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENT unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
■ ANGLE BRACKET
SCHEMATIC CIRCUITRY