ES-8212 Rev.1
MGD-65
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE & PULSE USE
(65 V DC; rack mounted)
Functions & Features
• Designed specifically for 4 – 20 mA DC and pulse signal line including both 4-wire and 2-wire transmitters
• Absorbing surges only without affecting instrumentation signal
• Rack-mounted
• Two channels in one housing
MODEL: MGD–65
ORDERING INFORMATION
• Code number: MGD-65
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals at the front; terminal cover provided
Connection
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Rack-mounted; Standard Rack Mounting Frame BX-16G available
Weight
: 200 g (0.44 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 70 V min.
Line to ground: ±500 V max.
Maximum surge voltage
Line to line: 80 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time
: ≤ 0.1 μsec.
Leakage current
:
Line to line: ≤ 5 μA @ 70 V DC
Line to ground: ≤ 5 μA @ ±140 V DC
Max. discharge current (Imax)
: 1000 A (8/ 20 μsec.)
Max. load current
: 100 mA
Internal series resistance
: Approx. 20 Ω including return
Maximum line voltage
: 70 V
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
■ ANGLE BRACKET
SCHEMATIC CIRCUITRY