ES-8182 Rev.1

MH-2201

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
POWER SUPPLY USE

(200 V / 220 V / 240 V AC, single phase)
Functions & Features
• Designed for installation where AC power enters the control panel for relatively large power consuming equipment such as large instrumentation panels, computer systems or telemetering systems in central control rooms or operation centers
• Composed of air-core reactors, large capacity discharge elements and electromagnetic contactors
• Thermal fuse in parallel with the discharge element opens and cuts off the operating circuit for the electromagnetic contactor in case of discharge elements failure, thus protecting the equipment connected to the arrester

MODEL: MH–2201

ORDERING INFORMATION

• Code number: MH-2201

GENERAL SPECIFICATIONS

Connection
  Primary side: M12 screw terminals
  Secondary side: M10 screw terminals
Screw terminal: Nickel-plated brass
Housing material: Steel plate t = 1.6 (black)

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface
Weight: 40 kg (88.2 lb)

PERFORMANCE

Discharge voltage (peak voltage)
  Line to line: 380 V min. 
  Line to ground: 410 V min.
Maximum surge voltage
  Line to line: 700 V max. 
  Line to ground: 700 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage  for very short time period.)
Response time: ≤ 0.1 μsec.
Leakage current
  Line to line: ≤ 1 A (at rated voltage, including relay coil current)
  Line to ground: ≤ 1 mA at 300 V DC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Maximum load current: 200 A
Voltage drop: ≤ 2 V (50/60 Hz)
Rated line voltage: 200 V / 220 V / 240 V AC

CONNECTION EXAMPLES

GROUNDING

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM