ES-8190 Rev.2
MH-230A
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE
(30 A, 200 V / 220 V / 240 V AC)
Functions & Features
• Designed specifically for power requirements of medium capacities
• Protecting electronic equipment from lightning surges that enter through substations and step-down transformers
• Discharge element failure triggers the fuse blown and alarm contact closed
• Also effective in rejecting switching transients generated by thyristors, circuit breakers, motor starters, etc.
Typical Applications
• Control panels
• Telemetering systems
MODEL: MH–230A
ORDERING INFORMATION
• Code number: MH-230A
GENERAL SPECIFICATIONS
Connection
: M4 screw terminals (torque 1.6 N·m)
Screw terminal
: Nickel-plated brass
Housing material
: Steel plate t = 1.6 (black)
Alarm indicator:
Discharge element failure indicator turns white when the fuse is blown.
Monitor lamp
: Red neon lamp turns on when the power is supplied.
Alarm relay contact
: Turns ON with discharge element failure (when the fuse is blown)
•
Rated load
: 100 V AC @ 250 mA (cos ø = 1)
100 V DC @ 250 mA (resistive load)
•
Maximum switching voltage
: 125 V AC or 125 V DC
•
Maximum switching power
: 25 VA or 25 W
•
Minimum load
: 5 V DC @ 10 mA
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface
Weight
: 3.7 kg (8.16 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 410 V min.
Line to ground: 410 V min.
Maximum surge voltage
Line to line: 700 V max.
Line to ground: 700 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time
: ≤ 0.1 μsec.
Leakage current
Line to line: ≤ 1 mA at 300 V DC
Line to ground: ≤ 1 mA at 300 V DC
Discharge current capacity:
10000 A (8/ 20 μsec.)
Maximum load current
: 30 A
Voltage drop
: ≤ 2 V (50/60 Hz)
Rated line voltage
: 200 V / 220 V / 240 V AC
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENT unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY