ES-1692 Rev.8

MNS

Plug-in Signal Conditioners M-UNIT

CONTACT ISOLATOR

(18 channels)
Functions & Features
• Galvanically isolating the output pulse from the input signal
• 18 channels housed in one module
• Isolation between input, output and power (non-isolated between each channel)
• High-density mounting
Typical Applications
• Isolating and sending 4-digit BCD signals from a digital panel meter to a PLC
• Multi-point isolation for low-speed pulse or digital (status) signals
 

MODEL: MNS–11[1]–[2][3]

ORDERING INFORMATION

• Code number: MNS-11[1]-[2][3]
Specify a code from below for each of [1] through [3].
  (e.g. MNS-111-B/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

INPUT

1: Dry contact

OUTPUT

1: Open collector

[1] OUTPUT LOGIC

1: Positive logic
2: Negative logic

[2] POWER INPUT

AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
DC Power
S: 12 V DC
R: 24 V DC
V: 48 V DC

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  Power input
: M3.5 screw terminals
  I/O: 40-pin connector
  (OTAX N365P040AU)
  (Fujitsu FCN-365P040-AU...discontinued)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Frequency range: Input and output are the same.

INPUT SPECIFICATIONS

Dry contact
Maximum frequency
: 100 Hz
Pulse width time requirement: 5 msec. min. for ON and OFF
Sensing: Approx. 12 V DC @ 1.5 mA
ON/OFF level: ≤200 Ω/0.3 V for ON, ≥100k Ω/11.1 V for OFF

OUTPUT SPECIFICATIONS

Open Collector
Maximum frequency
: 100 Hz
Rating: 30 V DC @ 10 mA per channel
Saturation voltage: 0.3 V DC

INSTALLATION

Power input
AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
DC: Operational voltage range: rating ±10 %,
ripple 10 %p-p max., approx. 2 W (80 mA at 24 V)
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @ 1 minute
(input to output to power)
2000 V AC @ 1 minute
(input or output or power to ground)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

I/O CONNECTOR PIN ASSIGNMENT