ES-4853 Rev.23
MSP6
ELECTRONIC ACTUATOR
MINI-TOP ELECTRONIC ACTUATOR
(linear type)
Functions & Features
• Small-size control valve actuator
• 1/1000 high resolution
• Seal-spring incorporated for both directions; usable with three-way valves
• Easy adjustment: electronic limiter at the valve open & closed positions
• Overload protection
• Various power inputs
Typical Applications
• Actuator for automatic control valve in pilot plants
• Air-conditioning in buildings or plants
• Micro-flow control for pharmaceutical injection
• For small-size control valves
MODEL: MSP6–[1][2][3][4]–[5][6][7][8]
ORDERING INFORMATION
• Code number: MSP6-[1][2][3][4]-[5][6][7][8]
Specify a code from below for each of [1] through [8].
(e.g. MSP6-361T-ACR/F/P/Q)
• Special input range (for codes Z and 0)
• Specify the specification for option code /Q
(e.g. /SET)
[1] STROKE
3
: 10 to 20 mm (.39” to .79”)
4
: 20 to 40 mm (.79” to 1.57”) (Not available for /P)
Y
: 10 to 22 mm (.39” to .87”) (Not available for /P)
For Japan sales only.
Select 'Y' when the yoke set (model: YSS-1) is used.
Must select '8: M8 female thread, 1.0 pitch' as [3] OUTPUT
STEM TYPE.
[2] OPERATION TIME, THRUST
3
: 5 sec. / 10 mm, 600 N
4
: 8 sec. / 10 mm, 1200 N
6
: 15 sec. / 10 mm, 2500 N
[3] OUTPUT STEM TYPE
6
: M6 female thread, 0.75 pitch
8
: M8 female thread, 1.0 pitch
1
: M10 female thread, 1.25 pitch
D
: M6 female thread, 1.0 pitch
E
: M8 female thread, 1.25 pitch
F
: M10 female thread, 1.5 pitch
[4] TERMINAL BOX
T
: With
0
: Without
[5] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Z
: Specify current (See INPUT SPECIFICATIONS)
Voltage
6
: 1 – 5 V DC (Input resistance approx. 1 MΩ)
0
: Specify voltage (See INPUT SPECIFICATIONS)
[6] CE & UKCA MARKING
C
: With CE and UKCA
0
: Without
[7] POWER SUPPLY VOLTAGE
AC Power
A
: 24 V AC (Operational voltage range 24 V ±10 %, 47 – 66 Hz)
(Not selectable for CE or UKCA)
K3
: 100 – 120 V AC
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
(Not selectable for CE and UKCA)
L3
: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)
(Not selectable for CE and UKCA)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[8] OPTIONS (multiple selections)
Control Signals
blank
: Without
/L
: Full-open/-closed signal
/F
: Forced open/close signal
/B
: Full-open/-closed and forced open/close signals
(Select ‘With Terminal Box.’)
Long-life Potentiometer
blank
: Standard potentiometer
/P
: Long-life potentiometer (for 20 mm stroke only)
(Not available when /L or /B is selected)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-4854)
GENERAL SPECIFICATIONS
Degree of protection
: IP66
Action
: Direct or Reverse; field selectable with DIP switches
Ex-factory setting: Reverse
In "Reverse" action, the output stem moves upward as the input signal increases when the actuator is mounted upright.
Operation at abnormally low input
:
- Retract/move upward
- Extend/move downward
- Stop
Ex-factory setting: Extend/move downward
(The operation direction of the output stem when the actuator is mounted upright)
Field selectable with DIP switches
Abnormal signal level
: -16 ±2.5 %
Electrical connection
•Without terminal box
Wiring conduit
: Cable connector with 1 m wire (0.5 mm
2
)
•With terminal box
(Sequential control signal suffix code: B)
Wiring conduit
: G 1/2 female (two)
Terminal screws
: M3 pillar terminal
•With terminal box
(Sequential control signal suffix code: other than B)
Wiring conduit
: G 1/2 female (two)
Terminal screws
: M3 chromated steel
(torque 0.5 N·m)
Housing material
: Diecast aluminum (ADC.12)
Drive
: Stepping motor
Insulation class
: E
Position detection
: Potentiometer
- Common specification (contact conductive)
Deadband
: 0.1 – 4.5 % adjustable
Ex-factory setting: 1.5 %
Restarting timer
: 0 – 10 sec.
Ex-factory setting: 1.5 sec.
Isolation
: AC power to signal
Zero adjustment
: 0 – 25 %
Span adjustment
: 50 - 100 %
Protective functions
: Overload (lock) protection
Power indicator
: Green LED is ON while power is supplied
Input indicator
: Green LED is ON while normal signal is input
Status indicator LED
: Red LED blinks at intervals of: 2 sec. in normal operation; and 0.5 sec. when an overload (lock) is detected
Manual operating handle
: Not available
Output stem operation distance and adjustable range
3: 10 - 20 mm
- Ex-factory setting: 0 - 20 mm
- Adjustable range: 0 - 10 mm (min. distance)
4: 20 - 40 mm (Not available for /P)
- Ex-factory setting: 0 - 40 mm
- Adjustable range: 0 - 20mm (min. distance)
Y: 10 - 22 mm (Not available for /P)
- Ex-factory setting: 0 - 20 mm
- Adjustable range: 0 - 22 mm (max. distance)
- Adjustable range: 0 - 10 mm (min. distance)
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated (250 Ω)
■
DC Voltage
: 1 – 5 V DC or specific range within 0 – 5 V DC, minimum span 1 V
(For a current input, convert the current to a voltage with 250 Ω)
Input resistance
: Approx. 1 MΩ
■
Forced open/close signal
: Dry contact inputs to command to go up and go down
Rating
: 5 V DC @ 2.5 mA
(go up and go down when upright mount)
OUTPUT SPECIFICATIONS
■
Operation Time & Torque
(at rated power voltage)
MSP6-x3: 5 sec. /10 mm 600 N (135 lbf)
MSP6-x4: 8 sec. /10 mm 1200 N (270 lbf)
MSP6-x6: 15 sec. /10 mm 2500 N (562 lbf)
■
DC Voltage
: 1 – 5 V DC (not isolated)
With “direct” action, 5 – 1 V DC position output is provided proportionally to 4 – 20 mA DC (1 – 5 V DC) input.
Load resistance
: ≥ 5 kΩ
■
Full-open / -closed signals
: Limit switch contact
Rating
: 125 V AC @ 0.75 A (cos ø = 1)
30 V DC @ 0.6 A (resistive load)
Mechanical life
: 3 × 10
7
cycles
Maximum operation frequency
: 60 cycles/min.
INSTALLATION
Power consumption
•
AC
:
25 VA
•
DC
: 0.6 A
(Current is approx. 1.5 times as high as the above figure during the motor startup)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 85 %RH (non-condensing)
Vibration
•Sweep endurance test
Acceleration: 2 G (19.6 m/s
2
)
Frequency: 10 to 1000 Hz
Cycle: 20 cycles
Rate: 1 Oct./min.
Endurance: approx. 4 hr. 30 min.
Direction: X, Y, Z
Mounting position
: All directions
However, DO NOT mount the actuator with its output stem or cable connector facing upward if the actuator is to be exposed to dripping water.
Weight
DC powered
: 3.5 kg (7.7 lb)
AC powered
: 3.6 kg (7.9 lb)
Add 0.5 kg (1.1 lb) for the terminal box.
PERFORMANCE
Resolution
: 1/1000 or 0.02 mm, whichever is greater, with a deadband of 0.1 %
Insulation resistance
•
AC powered
(100 V AC, 200 V AC)
:
≥ 100 MΩ with 500 V DC
(signal or metallic housing to power)
≥ 100 MΩ with 100 V DC
(signal to metallic housing)
•
AC powered
(24 V AC)
:
≥ 100 MΩ with 100 V DC
(signal or metallic housing to power)
•
DC powered
(24 V DC)
:
≥ 100 MΩ with 100 V DC
(signal or power to metallic housing)
Dielectric strength
•
AC powered (100 V AC, 200 V AC)
:
1500 V AC @ 1 minute
(signal or metallic housing to power)
100 V AC @ 1 minute
(signal to metallic housing)
•
AC powered (24 V AC)
:
1500 V AC @ 1 minute
(signal or metallic housing to power)
•
DC powered
(24 V DC)
:
100 V AC @ 1 minute
(signal or power to metallic housing)
STANDARDS & APPROVALS
■
EU conformity (CE marking)
•
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
•
Low Voltage Directive
EN 61010-1
Measurement Category II (125 V)
Reinforced insulation:
Full-open/-closed signal to other signals or power
Full-open/-closed signal to metal housing
Pollution Degree 2
•
RoHS Directive
EN IEC 63000
■
UK conformity (UKCA marking)
The UK legislations and designated standards equivalent
to the applicable EU directives.
TERMINOLOGY
•
Overload (Lock) Protection
The Mini-Top Series is equipped with a protection circuit against overload caused by for example the valve catching an alien substance.
When an overload is detected, the Mini-Top stops supplying power to the motor and the status LED blinks in 0.5 sec. intervals.
The protection is reset automatically with applying opposite-direction input signal or turning the power off and restarting.
•
Restarting Timer
The Mini-Top Series is equipped with a timer circuit which gives an interval period (0 – 10 seconds) between stop-restart actions to prevent the motor and other internal components from overheating.
It is recommended to set a long restarting time when the ambient temperature and/or the temperature of flow material is high.
•
Electronic Limiter
This model is equipped with electronic limiters in order to prevent mechanical locks when the input goes below 0 % or above 100 %.
Limiters are set at approx. -0.5 % for the full-closed side, approx. 100.5 % for the full-open side.
•
Seal-Spring
The Mini-top Series incorporates a seal-spring to maintain the sealing pressure when the valve is fully closed. The standard spring has 0.5 – 1 mm (.02” – .04”) flexibility to facilitate the full-closed adjustment.
TERMINAL CONNECTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY