ES-4864 Rev.5
MSP6C
ELECTRONIC ACTUATOR
MINI-TOP ELECTRONIC ACTUATOR
(linear type; CC-Link)
Functions & Features
•Small-size control valve actuator
•Direct connection to CC-Link capable PLC and other devices on the same network
•Easy wired
•Uploading device information via CC-Link for maintenance purpose
•1/1000 high resolution
Typical Applications
• For small size proportional control valve in paper manufacturing or co-generation system
• Air conditioning for buildings and factories
• Chemical injection at water treatment plant
MODEL: MSP6C–[1][2][3]–0R
ORDERING INFORMATION
• Code number: MSP6C-[1][2][3]-0R
Specify a code from below for each of [1] through [3].
(e.g. MSP6C-331-0R)
[1] STROKE
3
: 10 to 20 mm (.39” to .79”)
4
: 20 to 40 mm (.79” to 1.57”)
[2] OPERATION TIME, THRUST
3
: 5 sec. / 10 mm, 600 N
4
: 8 sec. / 10 mm, 1200 N
6
: 15 sec. / 10 mm, 2500 N
[3] OUTPUT STEM TYPE
6
: M6 female thread, 0.75 pitch
8
: M8 female thread, 1.0 pitch
1
: M10 female thread, 1.25 pitch
D
: M6 female thread, 1.0 pitch
E
: M8 female thread, 1.25 pitch
F
: M10 female thread, 1.5 pitch
CE MARKING
0
: Without
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Degree of protection
: IP66
Operation at a communication error
: Extend, retract or stop
Power circuit connection
: 4-core microconnector, male
Power cable
: Cable with connector (e.g. OMRON XS2F or XS2WD42)
Transmission cable
: Conforms to CC-Link
(TE Connectivity TAA545 or Phoenix Contact SAC-4P)
Housing material
: Cast aluminum
Drive
: Stepping motor
Insulation class
: E
Position detection
: Potentiometer
Deadband
: 0.1 – 1.9 % adjustable (factory set to 1.5 %)
Restarting timer
: 0 – 10 sec. adjustable
(factory set to 1.5 sec.)
Isolation
: Housing or communication to power
Zero adjustment
: 0 – 25 %
Span adjustment
: 50 - 100 %
Protective functions
: Overload protection
Status indicator LED
: Red light blinks in 2 sec. intervals in normal operations; blinks in 0.5 sec. intervals when a foreign object is detected mechanically caught inside.
Manual operating handle
: Not available
CC-Link COMMUNICATION
Protocol
: CC-Link V1.10
Device type
: Remote device station
Station No. setting
: Rotary switch; 1 – 64
Required node
: 1
Baud rate setting
: Rotary switch
L RUN indicator
: Red LED
L ERR. indicator
: Red LED
OUTPUT SPECIFICATIONS
■
Operation Time & Torque
(at rated power voltage)
[Model: Operation Time: Thrust]
MSP6C-x3: 5 sec. /10 mm 600 N (135 lbf)
MSP6C-x4: 8 sec. /10 mm 1200 N (270 lbf)
MSP6C-x6: 15 sec. /10 mm 2500 N (562 lbf)
INSTALLATION
Current consumption
•
DC
: Approx. 0.5 A
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 85 %RH (non-condensing)
Vibration
: 0.5 G (4.9 m/s
2
) max.
Mounting position
: All directions
Do not mount the actuator with its output stem or cable connector on the upside if the actuator is to be exposed to dripping water.
Weight:
2.8 kg (6.17 lb)
PERFORMANCE
Resolution
: 1/1000 or 0.015 mm, whichever is greater, with 0.1 % deadband setting
Insulation resistance
: ≥ 100 MΩ with 100 V DC
Dielectric strength
: 100 V AC @ 1 minute
(housing or communication to power)
COMMUNICATIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY