ES-1368 Rev.11
PDU
Plug-in Signal Conditioners M-UNIT
PULSE SCALER
(pulse dividing; selectable range)
Functions & Features
• Galvanically isolating pulse rate signals and converting them into convenient engineering unit
• Excitation
• Scaling factor adjustable with the front switches
• Uniform output pulse
• Various outputs (relay, open collector and voltage pulses)
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Positive displacement flowmeters and turbine meters
• Dry contact signal produced at rotating machine
MODEL: PDU–[1][2][3][4]–[5][6]
ORDERING INFORMATION
• Code number: PDU-[1][2][3][4]-[5][6]
Specify a code from below for each of [1] through [6].
(e.g. PDU-CM1N-B/Q)
• Use Ordering Information Sheet (No. ESU-1368). Default setting (table below) will be used if not otherwise specified.
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
A
: Dry contact
B
: Voltage pulse (Specify sensitivity)
C
: 5 V pulse (sensitivity 2 V)
D
: 12 V/24 V pulse (sensitivity 5 V)
H
: Two-wire current pulse
[2] OUTPUT
A
: Open collector (max. 100 kHz)
M
: 5 V pulse (max. 100 kHz)
N
: 12 V pulse (max. 100 kHz)
P
: 24 V pulse (max. 100 kHz)
H
: Relay contact (max. 5 Hz)
( ) = Max. frequency
[3] OUTPUT PULSE WIDTH
1
: One-shot output (5 – 200 μsec.)
(Not selectable with relay contact.)
2
: One-shot output (0.18 – 9 msec.)
(Not selectable with relay contact.)
3
: One-shot output (9 – 400 msec.)
[4] OUTPUT LOGIC
N
: The same as the input
R
: Inverted
[5] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
[6] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Input pulse sensing
: DC coupled
Sensitivity adjustment
: Single-turn screwdriver adjustment (front); 0 – ±7 V
Hysteresis (deadband): Approx. 0.5 V
Input filter
: Provided for 10 Hz or lower output frequency (time constant approx. 1 msec.)
Scaling factor adjustment
: 10-position rotary switches (front);
1 / ( m × 10
^n
) m = 1 - 9999, n = 0 - 6
Output pulse width adjustment
: Multi-turn screwdriver adjustment (front); 5 μsec. – 400 msec.
INPUT SPECIFICATIONS
Frequency range
: 0 – 100 kHz (10 Hz max. with filter)
Excitation
: 12 V DC @ 30 mA; shortcircuit protection
Pulse width time requirement
: 5 μsec. min. (10 ms with filter)
■
Dry Contact
Sensing
: 7.5V DC @ 1mA
ON/OFF level
: ≥ 30 kΩ/5 V for OFF; ≤ 1 kΩ/1 V for ON
■
Voltage Pulse
: Specify DC offset and amplitude.
Waveform
: Square or sine
Input impedance
: 10 kΩ min.
Input amplitude
: 2 – 50 Vp-p
Offset
: 0 – ±7 V
Max. voltage between input terminals
: ±32 V
•
5V, 12V, 24V Pulse
Waveform
: Square or sine
Input impedance
: 10 kΩ min.
Detecting level
(Input: 5 V pulse: 12 V/24 V pulse)
V
H
: ≥ 3 V: ≥ 6 V
V
L
: ≤ 1 V: ≤ 4 V
■
Two-wire Current Pulse
Input resistance
: Receiving resistor 220 Ω
Maximum current
: ±50 mA
Hi/Lo level
: ≤ 5 mA for Lo, ≥ 15 mA for Hi
OUTPUT SPECIFICATIONS
■
Open Collector
: 50 V DC @ 50 mA (resistive load)
Maximum frequency
: 100 kHz with load resistance ≤ 1 kΩ
Saturation voltage
: 1.0 V DC
■
Voltage Pulse
:
High level
: Rating (5, 12 or 24 V) ±10 %
Low level
: ≤ 0.5 V
Maximum frequency
: 100 kHz
Load resistance
:
1 kΩ min. for 5 V
2.4 kΩ min. for 12 V,
4.8 kΩ min. for 24 V
■
Relay Contact
:
120 V AC @ 200 mA (cos ø = 1)
30 V DC @ 200 mA (resistive load)
Electrical life 3 × 10
5
cycles (rate 30/min.)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 24 VA or 6 W
Minimum load
: 5 V DC @ 10 mA
Mechanical life
: 2 × 10
7
cycles
For maximum relay life with inductive loads, external protection is recommended.
Maximum frequency
: 5 Hz
OUTPUT PULSE WIDTH
•
One-shot Output
: Preset pulse width ±20 %;
The pulse width is factory set to approx. 50 % duty ratio at the maximum frequency. For relay output, it is limited within the range indicated in Code 3 specification.
Adjustable pulse width
: 5 μsec. – 400 msec.
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
•
DC
: Operational voltage range: rating ±10 %,
ripple 10 %p-p max., approx. 2 W (80 mA at 24 V)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE
Response time
:
≤ 25 μsec. without filter
≤ 2 msec. with filter
≤ 20 msec. with relay contact pulse
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
EXTERNAL VIEW
Note: This unit is factory calibrated according to the Ordering Information Sheet.
OUTPUT LOGIC
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM