ES-5660 Rev.21
R1M-A1/MSR
PC Recorders R1M Series
PC RECORDER
(contact input, 32 points)
Functions & Features
• Industrial recorder on PC
• 32-point dry contact inputs
• Easy system expansion via Modbus RTU
• Recorded data exportable to spreadsheet applications
MODEL: R1M-A1[1]-[2][3]
ORDERING INFORMATION
• Code number: R1M-A1[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. R1M-A1T-M2/MSR/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] FIELD TERMINAL TYPE
T
:
M3 screw terminals
C1
: FCN type connector (No CE conformance)
[2] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
PC Recorder Software Package (must be specified)
/MSR
: With
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable (model: FCN32)
PACKAGE INCLUDES...
• PC Recorder Software CD
• 9-pin D-sub connector, straight type (1 m or 3.3 ft)
GENERAL SPECIFICATIONS
Connection
Power input, transmission
: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 – 12), stripped
length 7 mm)
RS-232-C
: 9-pin D-sub connector (male)
(Lock screw No. 4-40 UNC)
Input
: M3 screw terminals (torque: 0.6N·m)
or FCN type connector (OTAX N364P032AU
(Fujitsu FCN-364P032-AU...discontinued))
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to RS-232-C or RS-485 to power
Count memory at power loss
: Count value is not saved when the power supply is lost.
Node address setting
: Rotary switch; 1 – F (15 nodes)
RUN indicator LED
: Green light blinks in normal conditions.
COMMUNICATION
Baud rate
: 38.4 kbps
Communication
: Half-duplex, asynchronous, no procedure
Protocol
: Modbus RTU
■
RS-232-C
Standard
: Conforms to RS-232-C, EIA
Transmission distance
: 10 meters max.
■
RS-485
Standard
: Conforms to TIA/EIA-485-A
Transmission distance
: 500 meters max.
Transmission media
: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
INPUT SPECIFICATIONS
Input
: Dry contact, 32 points
Commons
: All negatives
Sensing
: Approx. 5 V DC (pull-up resistance 22 kΩ)
≤ 1.5 V at ON
≥ 4 V at OFF
Sampling rate
: 50 msec.
•
Totalizing Counter Function
Number of input channels
: 16
(ch.1 thr. 16 available both with instantaneous status and totalized value)
Max. input frequency
: 100 Hz
Minimum pulse width
: 5 ms
Counter reset input
: Pulse rising (ch.32 assigned)
Max. counter value
: 999 999 999 (reset to zero at overflow)
INSTALLATION
Power consumption
•
AC
: Approx. 10 VA
•DC
: Approx. 7 W
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (0.88 lb)
PERFORMANCE
Multi-transmission time
: 5 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (input to RS-232-C or RS-485 to power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or RS-232-C/RS-485 to power: Reinforced insulation (300 V)
Input to RS-232-C/RS-485: Basic insulation (300 V)
RoHS Directive
PC RECORDER SOFTWARE
PC Recorder Software Package (model: MSRPAC-2010) is included with purchases of this model.
Refer to the MSRPAC-2010 data sheet for the contents of the package and the requirements for the PC to be prepared by the user.
EXTERNAL VIEW
MODBUS WIRING CONNECTION
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
■ M3 SCREW TERMINALS
■ FCN TYPE CONNECTOR
SYSTEM CONFIGURATION EXAMPLES