ES-9027 Rev.4
R30GCIE1
Remote I/O R30 Series
CC-Link INTERFACE MODULE
(CC-Link IE Field network)
Functions & Features
• Serves as a gateway for allowing CC-Link IE Field Network data to be handled by network modules that use different protocols.
• Recognized as an analog I/O mixed module by the network modules.
• Works as a slave station on CC-Link IE Field Network in the same manner as R30NCIE1.
Typical Applications
• A gateway for CC-Link IE Filed and EtherCAT.
MODEL: R30GCIE1S[1]
ORDERING INFORMATION
• Code number: R30GCIE1S[1]
Specify a code from below for [1].
(e.g. R30GCIE1S/Q)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S
: Single
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
・Please use this unit with a network module (model: R30NECT1) of firmware version V1.04.10 or higher, and a network module (model: R30NCIE1) of firmware version V1.01.13 or higher.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
CC-Link IE Field
: RJ-45 connector
Internal bus
: Via the Installation Base (model: R30BS)
I
nternal power
: Via the Installation Base (model: R30BS)
Isolation
: CC-Link IE Field to internal bus or internal power
Internal bus
communication cycle
:
Approx. 1 msec.
Status indicator
: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)
CC-Link IE Field COMMUNICATION
Protocol
: IEEE 802.3
Transmission type
: 1000BASE-T
Communication speed
: 1 Gbps
Network cable
: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology
: Line, star and ring
Max. number of stations
: 120 (Total slave stations)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance
: 100 m
Station type
: Remote device station
Link device
: RX/RY 128 points, RWw/RWr 64 points
NetWork No.
: 1 to 239 (factory default: 1)
INSTALLATION
Current consumption:
140 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 125 g (0.28 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (CC-Link IE Field to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
Number of transmission data: 4 points (4 words) for input; 4 points (4 words) for output
This unit is equivalent to an analog I/O mixed module (AIO4) of R30 series, and is recognized as an I/O module by Interface module (e.g. model: R30NECT1).
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SYSTEM CONFIGURATION EXAMPLES
The below figure shows a system configuration example in which CC-Link IE Field data is converted into EtherCAT data by using this unit as a gateway.