ES-8902 Rev.4

R30NCIT1

Remote I/O R30 Series

NETWORK MODULE

(CC-Link IE TSN)
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (CC-Link IE TSN)
• Combined with R3 Series I/O modules

MODEL: R30NCIT1[1]

ORDERING INFORMATION

• Code number: R30NCIT1[1]
Specify a code from below for [1].
  (e.g. R30NCIT1/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2 and R3S-CM2A)

GENERAL SPECIFICATIONS

Connection
  CC-Link IE TSN: RJ-45 connector
  Internal bus: Via the Installation Base (model: R30BS)
  Internal power: Via the Installation Base (model: R30BS)
Isolation: CC-Link IE TSN to internal bus or internal power
Input type & range:
 R30 series I/O module: PC configuration software (model: R30CFG)
 R3 series I/O module: PC configuration software (model: R3CON)
Internal bus communication cycle: Approx. 1 msec.
Status indicator: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)

CC-Link IE TSN

Protocol: IEEE 802.3
Transmission type: 1000BASE-T
Communication speed: 1 Gbps
Communication method: Time sharing method
Synchronization function: IEEE802.1AS and IEEE1588v2 compliant
Certification class: Class B
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology: Line, star and ring
Max. number stations: 64770 (Total master and slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance: 100 m
Station type: Remote station
Link device: RX/RY 112 points, RWw/RWr 64 points
(Number of points summation of I/O module for R30 series and R3 series)

INSTALLATION

Current consumption: ≤ 160 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 125 g (0.28 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE TSN to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
EMC Directive  
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

DATA ALLOCATION

This unit recognize type of I/O module (number of occupied station) configured the same base, and assign it to I/O Modules data with slot order automatically. However, I/O module assignment is performed only when power is turned on, in the case of changing configuration of I/O module, please turn on power again.
Keep number of station occupied of I/O module under 64, because max number of occupied station is 64 per a node. When the I/O module has space, data is transmitted close to HOST PC/PLC.
Station type: Remote station
Link device: RX/RY 128points, RWw/RWr 64points
(Points are total of R30 series and R3series module)

E.g. I/O data is assigned as shown below in the case of following configuration.
■ STATUS DATA

I/O DATA DESCRIPTIONS

OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.
■ MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
■ANALOG DATA (16-bit data, models: R30SV4, R30SV2, R30YV4, R30YS4, R30US4, etc.)
■ ANALOG DATA (16-bit data, models: R30RS4, R30TS4, R30US4, etc.)
■ ANALOG DATA (16-bit data, models: R30CT4E etc.)
■ ANALOG DATA (16-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ ANALOG DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R30XN16A, R30YN16x, etc.)

EXTERNAL DIMENSIONS unit: mm [inch]