ES-8902 Rev.4
R30NCIT1
Remote I/O R30 Series
NETWORK MODULE
(CC-Link IE TSN)
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (CC-Link IE TSN)
• Combined with R3 Series I/O modules
MODEL: R30NCIT1[1]
ORDERING INFORMATION
• Code number: R30NCIT1[1]
Specify a code from below for [1].
(e.g. R30NCIT1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2 and R3S-CM2A)
GENERAL SPECIFICATIONS
Connection
CC-Link IE TSN
: RJ-45 connector
Internal bus
: Via the Installation Base (model: R30BS)
I
nternal power
: Via the Installation Base (model: R30BS)
Isolation
: CC-Link IE TSN to internal bus or internal power
Input type & range
:
R30 series I/O module: PC configuration software (model: R30CFG)
R3 series I/O module: PC configuration software (model: R3CON)
Internal bus
communication cycle
:
Approx. 1 msec.
Status indicator
: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)
CC-Link IE TSN
Protocol
: IEEE 802.3
Transmission type
: 1000BASE-T
Communication speed
: 1 Gbps
Communication method
: Time sharing method
Synchronization function
: IEEE802.1AS and IEEE1588v2 compliant
Certification class:
Class B
Network cable
: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology
: Line, star and ring
Max. number stations
: 64770 (Total master and slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance
: 100 m
Station type
: Remote station
Link device
: RX/RY 112 points, RWw/RWr 64 points
(Number of points summation of I/O module for R30 series and R3 series)
INSTALLATION
Current consumption
: ≤ 160 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 125 g (0.28 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (CC-Link IE TSN to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
DATA ALLOCATION
This unit recognize type of I/O module (number of occupied station) configured the same base, and assign it to I/O Modules data with slot order automatically. However, I/O module assignment is performed only when power is turned on, in the case of changing configuration of I/O module, please turn on power again.
Keep number of station occupied of I/O module under 64, because max number of occupied station is 64 per a node. When the I/O module has space, data is transmitted close to HOST PC/PLC.
Station type: Remote station
Link device: RX/RY 128points, RWw/RWr 64points
(Points are total of R30 series and R3series module)
E.g. I/O data is assigned as shown below in the case of following configuration.
■ STATUS DATA
I/O DATA DESCRIPTIONS
■
OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.
■ MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
■ANALOG DATA (16-bit data, models: R30SV4, R30SV2, R30YV4, R30YS4, R30US4, etc.)
■ ANALOG DATA (16-bit data, models: R30RS4, R30TS4, R30US4, etc.)
■ ANALOG DATA (16-bit data, models: R30CT4E etc.)
■ ANALOG DATA (16-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ ANALOG DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R30XN16A, R30YN16x, etc.)
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM