ES-9019 Rev.5
R30NE1
Remote I/O R30 Series
MODBUS/TCP INTERFACE MODULE
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (Modbus/TCP)
• Combined with R3 Series I/O modules
MODEL: R30NE1[1]
ORDERING INFORMATION
• Code number: R30NE1[1]
Specify a code from below for [1].
(e.g. R30NE1/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9019)
CAUTION
• The internal bus communication period for R3 series I/O modules installed on the R30EBS is as follows.
Internal bus communication period = 6 msec. × number of I/O module + 10 msec. (Data update period of main CPU)
Example: Four R3 I/O modules
6 msec. × 4 + 10 msec. = 34 msec.
Even when the R30EBS is mounted to the R30BS, the internal bus communication period of R30 series is kept to approx. 1 msec.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2)
GENERAL SPECIFICATIONS
Connection
Ethernet
: RJ-45 connector
Internal bus
: Via the Installation Base (model: R30BS)
I
nternal power
: Via the Installation Base (model: R30BS)
Isolation
: Ethernet to internal bus or internal power
Setting input type & input range
:
R30 series I/O module: PC configuration software (model: R30CFG)
R3 series I/O module: PC configuration software (model: R3CON)
Internal bus
communication cycle
:
Approx. 1 msec.
Status indicator LEDs
: PWR, RUN, ERR
(Refer to the instruction manual for details.)
ETHERNET COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: Modbus/TCP
Data
: RTU (Binary)
Max. number of socket connections
: 2
Transmission media
: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
Ethernet indicator LEDs
: LINK10, LINK100
IP address
: 192.168.0.1 (factory setting);
can be set/changed using PC Configurator Software (model: R30CFG)
Port No
.: 502
INSTALLATION
Current consumption:
110 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 105 g (0.23 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
EXTERNAL VIEW
MODBUS FUNCTION CODES & SUPPORTED CODES
MODBUS I/O ASSIGNMENT
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R30SV2, R30SV4, R30YV4, R30YS4, R30US2, R30US4 etc.)
■ ANALOG DATA (16-bit data, models: R30RS4, R30TS4, R30US2, R30US4, etc.)
■ ANALOG DATA (16-bit data, models: R30CT4E etc.)
■ ANALOG DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ ANALOG DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R30XN16A, R30YN16A, R30YN16C etc.)
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM