ES-9007 Rev.6
R30PS1
Remote I/O R30 Series
POWER SUPPLY MODULE
(Current capacity 800 mA)
MODEL: R30PS1-R[1]
ORDERING INFORMATION
• Code number: R30PS1-R[1]
Specify a code from below for [1].
(e.g. R30PS1-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R30BS)
RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R30BS)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
(Solderless terminals with insulation sleeve do not fit.)
Applicable wire size
: 0.25 to 0.75 mm
2
Screw terminal
: Nickel-plated steel
Isolation
: Internal bus or internal power to power input to RUN contact output to FE
Power indicator LED
: Green LED turns on when the power is supplied.
RUN indicator LED
: Green LED turns on when the RUN contact output is closed.
■
RUN CONTACT OUTPUT
RUN contact output
: Turns ON (closed) while the network module operates normally.
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage:
250 V AC or 30 V DC
Maximum switching power:
250 VA or 30 W
Minimum load:
5 V DC @ 10 mA
Mechanical life:
2 × 10
7
cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
■Recommended solderless terminal size - M3 (unit: mm)
INSTALLATION
Power consumption
•
DC
: Approx. 21 W (approx. 0.9 A at 24 V)
Internal power
• Max. rated output voltage / current: 21 V DC / 800 mA
(The total current consumption of all mounted network and I/O modules must be within 800 mA.)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 150 g (0.33 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (internal bus or internal power to power input to RUN contact output to FE)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.