ES-9007 Rev.6

R30PS1

Remote I/O R30 Series

POWER SUPPLY MODULE

(Current capacity 800 mA)

MODEL: R30PS1-R[1]

ORDERING INFORMATION

• Code number: R30PS1-R[1]
Specify a code from below for [1].
  (e.g. R30PS1-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection
  
Internal bus: Via the Installation Base (model: R30BS)
  RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
  Internal power: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd. 
  (Solderless terminals with insulation sleeve do not fit.)
  Applicable wire size: 0.25 to 0.75 mm2
Screw terminal: Nickel-plated steel
Isolation: Internal bus or internal power to power input to RUN contact output to FE
Power indicator LED: Green LED turns on when the power is supplied.
RUN indicator LED: Green LED turns on when the RUN contact output is closed.
RUN CONTACT OUTPUT
RUN contact output: Turns ON (closed) while the network module operates normally.
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
■Recommended solderless terminal size - M3 (unit: mm)

INSTALLATION

Power consumption
DC: Approx. 21 W (approx. 0.9 A at 24 V)
Internal power
• Max. rated output voltage / current: 21 V DC / 800 mA
(The total current consumption of all mounted network and I/O modules must be within 800 mA.)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 150 g (0.33 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (internal bus or internal power to power input to RUN contact output to FE)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.