ES-9015 Rev.4
R30SV2
Remote I/O R30 Series
DC VOLTAGE/CURRENT INPUT MODULE
(2 points, isolated)
Functions & Features
• 2 channels for DC voltage/current input remote I/O module
• Isolation between input channels
• Input range of each channel is individually adjustable with PC configurator
MODEL: R30SV2S[1]
ORDERING INFORMATION
• Code number: R30SV2S[1]
Specify a code from below for [1].
(e.g. R30SV2S/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
2
: 2
COMMUNICATION MODE
S
: Single
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9015)
CAUTION
■
UNUSED INPUT CHANNELS
Set unused channels to "CH disabled" with PC Configurator software: R30CFG. When input range is 1 to 5 V DC or 4 to 20 mA DC, input values of the unused channels left open are to be lower than -15 %, which set a data error at the PLC or other host devices.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R30BS)
Input
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R30BS)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
(Solderless terminals with insulation sleeve do not fit.)
Applicable wire size
: 0.25 to 0.75 mm
2
Screw terminal
: Nickel-plated steel
Isolation
: Input 1 to input 2 to internal bus or internal power
Input range
: Selectable with PC configuration software (model: R30CFG)
Conversion rate
: Selectable with PC configuration software (model: R30CFG)
Status indicator LED
: RUN, ERR
(refer to the instruction manual)
■Recommended solderless terminal size - M3 (unit: mm)
INPUT SPECIFICATIONS
Module type
: Analog input, 2 points
■
DC Current
Input resistor: 70 Ω
Input range: :-20 to +20 mA DC, 0 to 20 mA DC,
4 to 20 mA DC
■
Narrow span voltage
Input resistance
: ≥ 100 kΩ
Input range
: :-1 to +1 V DC, 0 to 1 V DC, -0.5 to +0.5 V DC
■
Wide span voltage
Input resistance
: ≥ 1 MΩ
Input range
: :-10 to +10 V DC (*), -5 to +5 V DC,
0 to 10 V DC, 0 to 5 V DC, 1 to 5 V DC
(*) Factory setting
INSTALLATION
Current consumption
: 40 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 160 g (0.35 lb)
PERFORMANCE
Conversion rate / conversion accuracy
:
10 ms / ±0.8%, 20 ms / ±0.4%, 40 ms / ±0.2%, 80 ms / ±0.1% (*)
(*) Factory setting
Data range
: 0 – 10000 of the input range
Data allocation
: 2
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Input delay time
: 50 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
CONFIGURATOR SOFTWARE SETTING
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM