ES-9006 Rev.5
R30YS4
Remote I/O R30 Series
DC CURRENT OUTPUT MODULE
(4 points, isolated)
Functions & Features
• 4 channels for DC current output remote I/O module
• Isolation between output channels
MODEL: R30YS4S[1]
ORDERING INFORMATION
• Code number: R30YS4S[1]
Specify a code from below for [1].
(e.g. R30YS4S/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
4
: 4
COMMUNICATION MODE
S
: Single
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9006)
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R30BS)
Output
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R30BS)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
(Solderless terminals with insulation sleeve do not fit.)
Applicable wire size
: 0.25 to 0.75 mm
2
Screw terminal
: Nickel-plated steel
Isolation
: Output 1 to output 2 to output 3 to output 4 to internal bus or internal power
Output at the loss of communication
: Selectable with PC configurator software (Model: R30CFG, factory default: output hold)
Status indicator LED
: RUN, ERR
(refer to the instruction manual)
■Recommended solderless terminal size - M3 (unit: mm)
OUTPUT SPECIFICATIONS
Module type
: Analog output, 4 points
Output range
: 4 to 20 mA DC
Load resistance
: ≤ 550 Ω
Operational range
: -15 to +115 % of output range
INSTALLATION
Current consumption
: 120 mA max.
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 160 g (0.35 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Conversion rate
: 10 msec.
Data range
: 0 – 10000 of the output range
Data allocation
: 4
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Output delay time
: ≤ 250 msec. (0 - 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 1 to output 2 to output 3 to output 4 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated by the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■
Output at the loss of communication
• Output Hold
If the network module is in error, the module holds the signal at error and stands by until the communication recovers.
• Output set value
If the network module is in error, the module holds the signal at error or power up and stands by until the communication recovers. The the signal at error or power up is selectable with PC configurator software (Model: R30 CFG)
Not depending on output at the loss of communication setting,
when power up the module holds the signal at error or power up and stands by until the normal data is received.
■
OUTPUT WIRE BREAKDOWN DETECTION
In the case of wire breakdown, output error is detected.
Then, the ERR indicator LED blinks in red and the flag of error is set on the PLC etc.
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]