ES-8436 Rev.8
R3-AV8
Remote I/O R3 Series
DC VOLTAGE INPUT ALARM MODULE
(8 points, isolated)
MODEL: R3–AV8[1][2]
ORDERING INFORMATION
• Code number: R3-AV8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-AV8W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
8
: 8
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
■
UNUSED INPUT CHANNELS
Set the unused channels to the ranges other than 1 - 5 V. Otherwise, set them as "Unused" with PC Configurator software: R3CON. Unused channels left open with 1 – 5 V setting are equal to the input lower than -15 %, which sets a data abnormality at the PLC or the host device.
Open circuit with the input range set to ±10 V means 50 % of the full-scale. An alarm setpoint must be set to a value that does not trip an unwanted alarm.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to internal bus or internal power
Input range
: Selectable with the side DIP SW (per 4 channels)
Conversion rate
: Selectable with the side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response failure);
Green in normal operating conditions.
INPUT SPECIFICATIONS
■
Narrow Span
: -1 – +1 V, 0 – 1 V DC
Input resistance
: 100 kΩ min.
■
Wide Span
: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
Input resistance
: 1 MΩ min.
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 250 g (0.55 lb)
PERFORMANCE
Conversion accuracy
: Refer to the table at the end of this section.
Conversion rate
: 160 / 80 / 40 / 20 msec. selectable
Data range
: 0 – 10000 of the input range
Data allocation
: 4
Current consumption
: 100 mA
Temp. coefficient
: ±0.015 % /°C (±0.008 %/°F)
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1000 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
ALARM SETTING
The following parameters are programmable using the PC Configurator Software (model: R3CON).
■
ALARM TRIP POINT
(-15.00 to +115.00 %;
factory set to A1: 80.00, A2: 60.00, A3: 40.00, A4: 20.00)
Four alarm setpoints are selectable per each input.
■
ALARM TYPE
(High or Low; factory set to A1: High, A2: High, A3: Low,
A4: Low)
High or Low alarm is selectable for each alarm trip point.
High alarm
: An alarm is set when the input signal goes above the setpoint.
Low alarm
: An alarm is set when the input signal goes below the setpoint.
■
DEADBAND (HYSTERESIS)
(0.00 to 100.00 %; factory set to 5.00)
Deadband (deviation between the points where the alarm is set and reset) is selectable for each alarm trip point.
■
ALARM ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after the input has entered in the alarm range.
This setting is common to all 8 points.
■
POWER ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 5.0)
The alarm output start functioning in the preset time after the power has been turned on.
This setting is common to all 8 points.
■
ALARM HOLD TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is reset in shorter time.
This setting is common to all 8 points.
EXTERNAL VIEW
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. Two (2) word (16 bits × 2) data is transmitterd to the PLC or the host device via the R3 network module.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM