ES-8376 Rev.10
R3-DA16B
Remote I/O R3 Series
AC CONTACT INPUT MODULE
(Di 16 points)
MODEL: R3–DA16B[1][2]
ORDERING INFORMATION
• Code number: R3-DA16B[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-DA16BW/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
16
: 16
INPUT
B
: AC CONTACT INPUT
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Input to internal bus or internal power
Excitation monitor
: Selectable with side DIP switch; ON/OFF setting available
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator
: Red LED; turns on with the input ON.
INPUT SPECIFICATIONS
Number of input
: 16 points
Input voltage
: 100 – 132 V AC
Input resistance
: 12 kΩ (60 Hz), 15 kΩ (50 Hz)
Common
: All points (2 terminals)
ON voltage/current
: ≥ 80 V AC, ≥ 5 mA
OFF voltage/current
: ≤ 30 V AC, ≤ 1.7 mA
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
: 1
Current consumption
: 80 mA
Response time
: ≤ 0.1 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (contact input)
Pollution Degree 2
Input to internal bus or internal power: Reinforced insulation (150 V)
RoHS Directive
FUNCTIONS
•
Excitation Monitor ON
The input is held at the last status when the loss of excitation is detected. The excitation must be connected across the terminal 9 (19) and 10 (20).
•
Excitation Monitor OFF
All input signals are turned off when the loss of excitation is detected.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM