ES-8462 Rev.8

R3-GC1

Remote I/O R3 Series

CC-Link INTERFACE MODULE

(CC-Link Ver.1.10/Ver.2.00)
Functions & Features
• Enables other protocol interface modules to communicate with CC-Link data (gateway).
• Recognized as an analog I/O mixed module by other protocol interface modules.
Typical Applications
• A gateway for CC-Link and Modbus.
 

MODEL: R3-GC1S[1]

ORDERING INFORMATION

• Code number: R3-GC1S[1]
Specify a code from below for [1]. 
  (e.g. R3-GC1S/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

COMMUNICATION MODE

S: Single

[1] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

CAUTION

• When selecting network modules, note that this unit is not designed to be used with network modules of certain types or versions.
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx, and R3-NLx.
• This unit CAN be used with:
   R3-NM3 and R3-NML3 of firmware version V1.00 or higher;
   R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1, 
   R3-NM4, and R3-NP1 of firmware version V2.00 or higher;
   and 
   other models of any firmware versions.

PACKAGE INCLUDES...

• Terminating resistor (110 Ω, 0.5 W)

GENERAL SPECIFICATIONS

Connection
  Network
: Euro type connector terminal
  (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
  Internal bus: Via the Installation Base
  (model: R3-BSx)
  Internal Power: Via the Installation Base
  (model: R3-BSx)
  RUN contact output: M3 separable screw terminal
  (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: CC-Link to internal bus or internal power to RUN contact output
RUN indicator: Bi-color (green/red) LED
Green turns ON when CC-Link communication is normal and fieldbus communication on the R3 Network module side is also normal; or
Red turns ON when receiving data.
Indication selectable with DIP SW3-4.
ERR indicator: Bi-color (green/red) LED
Green turns ON/blinks in communication errors (OFF with wire breakdown; Green blinks with setting errors); or
Red turns ON when transmitting data.
Indication selectable with DIP SW3-4.
RUN CONTACT OUTPUT
RUN contact: Turns on while the green RUN LED is ON
(only when CC-Link communication and the
field bus built-in the interface module are in normal).
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

CC-Link COMMUNICATION

CC-Link: Both Version 1.10 and Version 2.00 are available.
Select the version with DIP SW3.
Cyclic expansion: 2, 4, 8 folds (Function selected with DIP
SW)
Station No. setting: Rotary switch; 1 – 64
Baud rate setting: Rotary switch
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps
Station type: Remote device station
Required nodes: 4
 Ver.1.10: (128 I/O points, 16 words)
 Ver.2.00: (112 I/O points, 16 words) × m (m = expanded
cyclic setting)
Transmission cable: Approved for CC-Link

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation
  Ver.1.10
: 16
  Ver.2.00: 16 × m (m = expanded cyclic setting)
Current consumption: 120 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(CC-Link to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TRANSMISSION DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

SYSTEM CONFIGURATION EXAMPLES

In the following system configuration, PC Recorder software captures the CC-Link data via R3-GC1 which is used as a gateway.