ES-8462 Rev.8
R3-GC1
Remote I/O R3 Series
CC-Link INTERFACE MODULE
(CC-Link Ver.1.10/Ver.2.00)
Functions & Features
• Enables other protocol interface modules to communicate with CC-Link data (gateway).
• Recognized as an analog I/O mixed module by other protocol interface modules.
Typical Applications
• A gateway for CC-Link and Modbus.
MODEL: R3-GC1S[1]
ORDERING INFORMATION
• Code number: R3-GC1S[1]
Specify a code from below for [1].
(e.g. R3-GC1S/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S
: Single
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
• When selecting network modules, note that this unit is not designed to be used with network modules of certain types or versions.
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx, and R3-NLx.
• This unit CAN be used with:
R3-NM3 and R3-NML3 of firmware version V1.00 or higher;
R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1,
R3-NM4, and R3-NP1 of firmware version V2.00 or higher;
and
other models of any firmware versions.
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Connection
Network
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Internal bus
: Via the Installation Base
(model: R3-BSx)
Internal
Power
: Via the Installation Base
(model: R3-BSx)
RUN contact output
: M3 separable screw terminal
(torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: CC-Link to internal bus or internal power to RUN contact output
RUN indicator:
Bi-color (green/red) LED
Green turns ON when CC-Link communication is normal and fieldbus communication on the R3 Network module side is also normal; or
Red turns ON when receiving data.
Indication selectable with DIP SW3-4.
ERR indicator
: Bi-color (green/red) LED
Green turns ON/blinks in communication errors (OFF with wire breakdown; Green blinks with setting errors); or
Red turns ON when transmitting data.
Indication selectable with DIP SW3-4.
■
RUN CONTACT OUTPUT
RUN contact
: Turns on while the green RUN LED is ON
(only when CC-Link communication and the
field bus built-in the interface module are in normal).
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA or 150 W
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
CC-Link COMMUNICATION
CC-Link
: Both Version 1.10 and Version 2.00 are available.
Select the version with DIP SW3.
Cyclic expansion
: 2, 4, 8 folds (Function selected with DIP
SW)
Station No. setting
: Rotary switch; 1 – 64
Baud rate setting
: Rotary switch
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps
Station type
: Remote device station
Required nodes
: 4
Ver.1.10
: (128 I/O points, 16 words)
Ver.2.00
: (112 I/O points, 16 words) × m (m = expanded
cyclic setting)
Transmission cable
: Approved for CC-Link
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
Ver.1.10
: 16
Ver.2.00
: 16 × m (m = expanded cyclic setting)
Current consumption
: 120 mA
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(CC-Link to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TRANSMISSION DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SYSTEM CONFIGURATION EXAMPLES
In the following system configuration, PC Recorder software captures the CC-Link data via R3-GC1 which is used as a gateway.