ES-8461 Rev.14
R3-GFL1
Remote I/O R3 Series
FL-net INTERFACE MODULE
(OPCN-2, Ver.2.0 supported)
Functions & Features
• Usable as a gateway between different protocols combined with R3 interface modules
• FL-net (OPCN-2), Ethernet based, controller level network, compatible remote I/O
• 10 Mbps/100 Mbps cyclic transmission for the maximum of 4k bits + 256 words (1 word = 16 bits) allows data shared among the devices connected to the bus
• FL-net bus extended to max. 500 meters, up to 2.5 kilometers with a repeater
• No need of ladder programming
Typical Applications
• A gateway between FL-net and Modbus
MODEL: R3-GFL1S[1]
ORDERING INFORMATION
• Code number: R3-GFL1S[1]
Specify a code from below for [1].
(e.g. R3-GFL1S/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S
: Single
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
FUNCTIONS & FEATURES
■ R3-GFL1 enables the other interface module to access field signals as virtual I/O data via FL-net. No ladder programming is required to assign these I/O signals.
■ Any PC or PLC compatible with FL-net, up to 254 nodes, can retrieve the updated data by accessing the common memory without interfering with the communication traffic.
■ Analog and discrete input signals cyclically transmitted from other devices can be output as virtual analog signal.
The FL-net Configuration Builder software (model: R3-NFLBLD) is used to assign these virtual analog signals on the common memory in the bit or word units.
■ Request/Response type message communication, accessing I/O data only when necessary, is also possible.
CAUTION !
• FL-net standard requires a dedicated Ethernet bus for the FL-net compatible devices. Connecting the R3-GFL1 to a general-purpose LAN, or connecting a general-purpose TCP/IP device to FL-net is Not allowed.
• FL-net uses UDP/IP protocol for transmission. ISDN, ADSL or similar types of LAN are Not to be used.
CAUTION
• When selecting network modules, note that this unit is not designed to be used with network modules of certain types or versions.
• This unit CANNOT be used with R3-NC2, R3-NEIP1, R3-NFx, and R3-NLx.
• This unit CAN be used with:
R3-NM3 and R3-NML3 of firmware version V1.00 or higher;
R3-NC1, R3-NC3, R3-NDx, R3-NE1, R3-NFL1, R3-NM1,
R3-NM4, and R3-NP1 of firmware version V2.00 or higher;
and
other models of any firmware versions.
RELATED PRODUCTS
• FL-net configuration builder (Model: R3-NFLBLD)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
FL-net
: RJ-45 connector
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal p
ower
: Via the Installation Base (model: R3-BSx)
RUN contact output
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
RUN/CFG selector
: Toggle switch; RUN or Configuration
Isolation
: Ethernet to internal bus or internal power to RUN contact output
Indicator LEDs
RUN
: Green LED turns on when the CPU, internal bus and
field bus on the other interface module are in normal
conditions.
ERR
: Red LED turns on in an abnormality of the system.
LNK
: Red LED turns on while the R3-GFL1 is participating
FL-net (normal communication)
HER
: Red LED turns on in an abnormality of I/O data.
PER
: Red LED blinks on with the parameter setting error.
CFG
: Red LED blinks in high speed at the startup; blinks in
low speed while the builder software is used.
TX
: Green LED turns on while transmitting.
RX
: Amber LED turns on while receiving.
Module allocation
: Set with the side DIP switch.
■
RUN CONTACT OUTPUT
RUN contact
: Relay turns on when the CPU, the internal bus function and the field bus on the other interface module are in normal conditions.
Rated load
: 250 V AC @0.5A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(< 50 V AC, < 75 V DC for EU conformity)
Maximum switching voltage
: 250 V AC or 220 V DC
Maximum switching power
: 62.5 VA or 60 W
Minimum load
: 10 mV DC @ 1 mA
Mechanical life
: 5 × 10
7
cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching are recommended.
FL-net SPECIFICATIONS
FL-net
: Ver.2.0 supported
Physical layer standard
: IEEE 802.3u
Data link layer
: 10BASE-T / 100BASE-TX
Baud rate
: 10 / 100 Mbps, Auto Negotiation
Protocol
: FL-net (OPCN-2) (UDP/IP)
Transmission media
: 10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length
: 100 meters
Max. number of nodes
: 254
IP address
: FL-net Configuration Builder is used to set up the IP address and the network address.
Factory setting
:
192.168.250.1 (IP address)
255.255.255.0 (network address)
Max. cyclic data size
:
8 k bits (area 1) + 8 k words (area 2) / system
4 k bits (area 1) + 256 words (area 2) / node
Max. message data size
: 1024 bytes (per transmission cycle)
Performance
(2k bits + 2k words / node, 32 nodes in total)
Token cycle time
: 50 milliseconds (1.56 milliseconds/ node in average)
Message transmission time
: 500 milliseconds (1 : 1 unidirectional message)
INSTALLATION
Current consumption
: 150 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
: 16 × n (Module allocation: 1 to 8)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FL-net DESCRIPTIONS
■
CYCLIC TRANSMISSION
• Transmitting virtual I/O value, this module's information and node error of signal source.
• Supplying common memory word data transmitted from another devices as virtual output.
• If the node that this module is accessing has been removed from the common memory, the operations “Hold output” and “Clear Output” are selectable.
■
MESSAGE TRANSMISSION
The module supports the FL-net defined functions listed in the following table. Only the server function is supported.
Server function allows the module to build a response frame to a request message.
Client function allows the module to transmit a request message and to receive its response frame.
PC REQUIREMENTS (provided by the user)
The following PC environment is required to run the R3-NFLBLD program.
Operating system
: Windows 7 (32-bit/64-bit) or Windows 10 (32-bit/64-bit)
Screen area
: 1024 by 768 pixels
LAN card
: Required to connect to Ethernet
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
Use the DIP SW located at the side of the module to specify module allocation.
1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 8 modules (128 words input, 128 words output) transmission is available. R3-GFL1 seems as if max. 8 I/O modules are mounted to 8 slots via FL-net.
The input of the module is processed as follows.
[FL-net Communication] --> [R3-GFL1 Module] --> [R3 Base] --> [R3 Communication Module]
The data set with output tab of R3-NFLBLD to input is transmitted to R3 communication module. Output is reversed. The data set with transmitting area 1 and transmitting area 2 is transmitted to FL-net.
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot, an internal bus error occurs. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the data for more than 16 modules.
■
WHEN R3-GFL1 IS MOUNTED ON SLOT NO. 2 (4 modules)
Real I/O modules are mounted on Slots No. 1 and 2, however, the network module (R3-NE1) recognizes that each of Slots No. 1 to 5 is occupied. That is, R3-NE1 recognizes R3-SV4 mounted on Slot No.1 as it is and recognizes R3-GFL1 mounted on Slot No.2 as divided into four modules and occupying Slots No. 2 to 5.
I/O DATA DESCRIPTIONS
■ MODULE STATUS, SOURCE NODE ERROR
■ ANALOG DATA
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SYSTEM CONFIGURATION EXAMPLES