ES-8275 Rev.3
R3-GSLMP1
Remote I/O R3 Series
INTERFACE I/O MODULE
(For SLMP Client)
Functions & Features
• Serves as a gateway for allowing data of SLMP-compatible devices to be handled by Network module that uses a different protocol.
• Reads/writes data from/to the SLMP server.
• Recognized as analog and/or discrete I/O modules by Network module according to the device configuration.
Typical Applications
• A gateway between SLMP and CC-Link.
MODEL: R3-GSLMP1S[1]
ORDERING INFORMATION
• Code number: R3-GSLMP1S[1]
Specify a code from below for [1].
(e.g. R3-GSLMP1S/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S
: Single
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R3CON version 2.55 or later)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
Ethernet
: RJ-45 Modular Jack
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal power
: Via the Installation Base (model: R3-BSx)
RUN contact output
: M3 separable screw terminal
(torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: Ethernet to internal bus or internal power to RUN contact output
RUN indicator:
Bi-color (green/red) LED
Green turns ON when SLMP communication is normal and fieldbus communication on the R3 Network module side is also normal; or
Red turns ON when receiving data.
(Indication selectable with DIP SW3-4.)
ERR indicator
: Bi-color (green/red) LED
Green turns ON/blinks in communication errors (OFF with wire breakdown; Green blinks with setting errors); or
Red turns ON when transmitting data.
(Indication selectable with DIP SW3-4.)
■
RUN CONTACT OUTPUT
RUN contact
: Turns on while the green RUN LED is ON (only when SLMP communication is normal and fieldbus communication on the R3 Network module side is also normal).
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA (AC) or 150 W (DC)
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching are recommended.
ETHERNET COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: SLMP
Data
: Binary
Max. number of socket connections
: 1
Max. number of communication entries
: 16
Max. number of I/O signals
: 128 points (total of analog and discrete signals)
Transmission media
: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Max. number of virtual I/O modules
: 16
Ethernet indicator LED
: LINK, DPLX, LINK10, LINK100, COL
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.1 (factory setting);
Selectable with PC Configurator Software (model: R3CON)
Connectable devices
: MELSEC iQ-R series, MELSEC iQ-F series, MELSEC Q series
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data Allocation (No. of Occupied Data Areas)
Virtual AI module: 16
Virtual AO module: 16
Virtual DI module: 1
Virtual DO module: 1
Current consumption
: 100 mA
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SYSTEM CONFIGURATION EXAMPLES