ES-8287 Rev.5

R3-NCIE1

Remote I/O R3 Series

NETWORK INTERFACE MODULE

(CC-Link IE Field network)

MODEL: R3-NCIE1[1]

ORDERING INFORMATION

• Code number: R3-NCIE1[1]
Specify a code from below for [1].
  (e.g. R3-NCIE1/CE/W/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Mitsubishi PLC Redundant System
blank: Without
/W: With
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC configurator software (model: R3CON)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
  CC-Link IE Field
: RJ-45 Modular Jack
  Internal bus: Via the Installation Base (model: R3-BSx)
  Internal power: Via the Installation Base (model: R3-BSx)
  RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: CC-Link IE Field to internal bus or internal power to RUN contact output 
Input error data setting: Input value setting at input module error with side DIP SW
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN indicator: Green LED ON at normal operating
ERR indicator: Red LED ON at abnormal node
RUN CONTACT OUTPUT
RUN contact: Turns ON while the green RUN LED is ON (ON in normal operation).
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

CC-Link IE Field COMMUNICATION

Protocol: IEEE 802.3
Transmission type: 1000BASE-T
Communication speed: 1 Gbps
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology: Line, star and ring
Max. number stations: 120 (Total slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
NetWork No.: 1 to 239; Selectable with PC Configurator Software (model: R3CON) (factory default: 1)

INSTALLATION

Current consumption: 170 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 190 g (0.42 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE Field to internal bus or internal power to RUN contact output)
1500 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TRANSMISSION DATA DESCRIPTIONS

Number of transmission data (data allocation) for each I/O module is set with the DIP switch on the side of the unit. Data allocation is assigned from slot 1 in sequence.
Keep number of transmission data of I/O module under 64, because max. number of transmission data is 64 per a node.
Station type: Remote device station
Link device: RX/RY 128points, RWw/RWr 64points
E.g. I/O data is assigned as shown below in the case of following configuration.
■ REMOTE INPUT

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

■ OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM