ES-8274 Rev.1

R3-NECT1

Remote I/O R3 Series

NETWORK INTERFACE MODULE

(EtherCAT)
EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.

MODEL: R3-NECT1[1]

ORDERING INFORMATION

• Code number: R3-NECT1[1]
Specify a code from below for [1].
  (e.g. R3-NECT1/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC configurator software (model: R3CON)
• ESI file
The configurator software and ESI files are downloadable at our web site.
Use a commercially available Mini-B USB cable to connect the unit to a PC.

GENERAL SPECIFICATIONS

Connection
  EtherCAT
: RJ-45 Modular Jack
  Internal bus: Via the Installation Base (model: R3-BSx)
  Internal power: Via the Installation Base (model: R3-BSx)
  RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: EtherCAT to internal bus or internal power to RUN contact output 
Input error data setting: Input value setting at input module error with side DIP SW
Dual communication setting: Set with the side DIP switch
Status indicators: RUN, ERR, L/A IN, L/A OUT
(Refer to the instruction manual.)
RUN CONTACT OUTPUT
RUN contact: Turns ON while the green RUN LED is ON (ON in normal operation).
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

EtherCAT COMMUNICATION

Standard: IEEE 802.3u
Transmission type: 100BASE-TX
Transmission speed: Full-duplex 100 Mbps
Transmission media: 100BASE-TX (STP cable; Category 5e)
Maximum segment length: 100 meters
Fixed address: Set with rotary switches
(The master must support MDP.)

INSTALLATION

Current consumption: 100 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 170 g (0.37 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (EtherCAT to internal bus or internal power to RUN contact output)
1500 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

■ OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM