ES-8466 Rev.7

R3-NEIP1

Remote I/O R3 Series

EtherNet/IP INTERFACE MODULE

Functions & Features
• Converts analog and discrete I/O data to the open network fieldbus (EtherNet/IP)
Typical Applications
• Remote I/O for DCS and PLC
 

MODEL:R3–NEIP1[1]

ORDERING INFORMATION

• Code number: R3-NEIP1[1]
Specify a code from below for [1].
  (e.g. R3-NEIP1/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC configurator software (model: R3CON)
• EDS file
The EDS file and configurator software are downloadable at our web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS

Connection
  Ethernet
: RJ-45 Modular Jack
  Internal bus: Via the Installation Base (model: R3-BSx)
  Internal power: Via the Installation Base (model: R3-BSx)
  RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: EtherNet/IP to internal bus or internal power to RUN contact output
Input error data setting: Input value setting at input module error with side DIP SW
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN CONTACT OUTPUT
RUN contact
: Turns ON when both MS and NS LEDs are green (EtherNet/IP in normal communication).
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

EtherNet/IP COMMUNICATION

Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Max. number of socket connections: 3
Connection type: Exclusive owner, Listen only, Input only
Protocol: EtherNet/IP
Transmission media: 10BASE-T (STP, Category 5) 100BASETX (STP, Category 5e)
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.1 (factory setting); Selectable with PC Configurator Software (model: R3CON)
BOOTP and DHCP available
Port No.: 44818
I/O data area size: Input and output data area size set with side DIP SW 
Required data words
 Input: 35, 67, 131, 252 words
 Output: 35, 67, 131, 252 words (3 words are used only for status)
Ethernet indicator LED:  TX/RX, LINK
MS (Module Status) indicator: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red) LED indicates status of the communication link.
Note: Not connectable beyond router.

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Current consumption: 130 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(EtherNet/IP to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TRANSMISSION DATA DESCRIPTIONS

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

SYSTEM CONFIGURATION EXAMPLES