ES-8288 Rev.3
R3-NF3
Remote I/O R3 Series
T-Link INTERFACE MODULE
(Fuji Electric T-Link capsule equivalent)
MODEL: R3–NF3–[1][2]
ORDERING INFORMATION
• Code number: R3-NF3-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NF3-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
N:
No power supply
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)*
DC Power
R:
24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or network modules with the internal power input options.
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
T-Link
: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Internal bus
: Via the Installation Base
(model: R3-BSx)
Internal
power
: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: T-Link to internal bus or internal power to power input to RUN contact output to FG
Input error data setting
: Input value setting at input module error with side DIP SW
Dual communication setting
: Set with the side DIP switch
Data allocation setting
: Set with the side DIP switch
I/O Points setting
: Set with the front DIP switch
Data setting
: Set with the front DIP switch
I/O Module Status setting
: Set with the front DIP switch
I/O Type setting
: Set with the front DIP switch
Analog Data Type setting
: Set with the front DIP switch
RUN indicator:
Bi-color (green/red) LED; Green ON in normal communication; Red blinks when receiving data (Function selected with DIP SW)
ERR indicator:
Bi-color (green/red) LED; Green ON in communication errors or minor failure, blinks at errors in the internal circuits; Red blinks when transmitting data (Function selected with DIP SW)
■
RUN CONTACT OUTPUT
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage:
250 V AC or 30 V DC
Maximum switching power:
250 VA or 150 W
Minimum load:
1 V DC @ 1 mA
Mechanical life:
2 × 10
7
cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
T-Link SPECIFICATIONS
Node address
: Rotary switch; 00 – 99
Configuration
: Multi-drop
Communication
: Half-duplex
Baud rate
: 500 kbps
Transmission media/distance
:
KPEV-SB, 0.75 mm
2
× 1 pair, 700 m
T-KPEV-SB, 1.25 mm
2
× 1 pair, 1000 m
INSTALLATION
Power consumption
•
AC:
≤ 22 VA
•
DC
: ≤ 9 W
Current consumption (no power supply):
120 mA
Output current (power supply)
: 230 mA continuous at 20 V DC; 380 mA for 10 minutes
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (T-Link to internal bus or internal power to power input to RUN contact output to FG)
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
MODULE STATUS, ERROR STATUS
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ ANALOG 16 BITS BCD DATA
■ ANALOG 32 BITS BCD DATA
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM