ES-8426 Rev.15
R3-NFL1
Remote I/O R3 Series
FL-net INTERFACE MODULE
(OPCN-2, Ver.2.0 supported)
Functions & Features
• FL-net (OPCN-2), Ethernet based, controller level network, compatible remote I/O
• 10 Mbps/100 Mbps cyclic transmission for the maximum of 4k bits + 256 words (1 word = 16 bits) allows data shared among the devices connected to the bus
• FL-net bus extended to max. 500 meters, up to 2.5 kilometers with a repeater
• I/O data can be assigned to any bits or words in the common memory
• No need of ladder programming
• Request/response type data access of message transmission is also possible
• Any other network module can be assigned to the dual redundant internal bus
• Supports multiple protocol of FL-net plus DeviceNet, CC-Link, and others
• Masterless configuration allows the FL-net I/Os function as local multiplex transmission system
MODEL: R3–NFL1[1]
ORDERING INFORMATION
• Code number: R3-NFL1-[1]
Specify a code from below for [1].
(e.g. R3-NFL1/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
FUNCTIONS & FEATURES
■ The R3-NFL1 is used to access field signals at the R3 I/O modules via FL-net.
No ladder programming is required to assign these I/O signals.
■ Analog and discrete input signals are transmitted cyclically.
Any PC or PLC compatible with FL-net, up to 254 nodes, can retrieve the updated data by accessing the common memory without interfering with the communication traffic.
■ Analog and discrete input signals cyclically transmitted from other devices can be output at the R3 output modules.
The FL-net Configuration Builder software (model: R3-NFLBLD) is used to assign these I/O signals on the common memory in the bit or word units.
■ The R3-NFL1, constantly scanning its I/O modules via the internal bus, has the updated data always ready for a request from the FL-net. High speed response without any loss time is possible.
■ Request/Response type message communication, accessing I/O data only when necessary, is also possible.
■ Dual redundant network configuration using two network modules is available.
Two different network protocols, e.g. FL-net and DeviceNet or FL-net and CC-Link, can be used to access one field signal.
■ Masterless configuration allows two FL-net nodes function as local multiplex transmission system.
CAUTION !
• FL-net standard requires a dedicated Ethernet bus for the FL-net compatible devices. Connecting the R3-NFL1 to a general-purpose LAN, or connecting a general-purpose
TCP/IP device to FL-net is Not allowed.
• FL-net uses UDP/IP protocol for transmission. ISDN, ADSL or similar types of LAN are Not to be used.
RELATED PRODUCTS
• FL-net configuration builder (Model: R3-NFLBLD)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
FL-net
: RJ-45 connector
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal p
ower
: Via the Installation Base (model: R3-BSx)
RUN contact output
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
RUN/CFG selector
: Toggle switch; RUN or Configuration
Isolation
: Ethernet to internal bus or internal power to RUN contact output
Dual communication setting
: Set with the side DIP switch
Indicator LEDs
PWR
: Green LED turns on when the CPU and the internal
bus function normally.
ERR
: Red LED turns on in an abnormality of the system.
LNK
: Red LED turns on while the R3-NFL1 is participating
FL-net (normal communication)
HER
: Red LED turns on in an abnormality of I/O data.
PER
: Red LED blinks on with the parameter setting error.
CFG
: Red LED blinks in high speed at the startup; blinks in
low speed while the builder software is used.
TX
: Green LED turns on while transmitting.
RX
: Amber LED turns on while receiving.
■
RUN Contact output
RUN contact
: Relay turns on when the CPU and the internal bus function normally.
Rated load
: 100 V AC @ 0.5A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(< 50 V AC, < 75 V DC for EU conformity)
Maximum switching voltage
: 250 V AC or 220 V DC
Maximum switching power
: 62.5 VA or 60 W
Minimum load
: 10 mV DC @ 1 mA
Mechanical life
: 5 × 10
7
cycles.
FL-net SPECIFICATIONS
FL-net
: Ver.2.0 supported
Physical layer standard
: IEEE 802.3u
Data link layer
: 10BASE-T / 100BASE-TX
Baud rate
: 10 / 100 Mbps, Auto Negotiation
Protocol
: FL-net (OPCN-2) (UDP/IP)
Transmission media
: 10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length
: 100 meters
Max. number of nodes
: 254
IP address
: FL-net Configuration Builder is used to set up the IP address and the network address.
Factory setting
:
192.168.250.1 (IP address)
255.255.255.0 (network address)
Max. cyclic data size
:
8 k bits (area 1) + 8 k words (area 2) / system
4 k bits (area 1) + 256 words (area 2) / node
Max. message data size
: 1024 bytes (per transmission cycle)
Performance
(2k bits + 2k words / node, 32 nodes in total)
Token cycle time
: 50 milliseconds (1.56 milliseconds/ node in average)
Message transmission time
: 500 milliseconds (1 : 1 unidirectional message)
INSTALLATION
Current consumption:
130 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FL-net DESCRIPTIONS
■
CYCLIC TRANSMISSION
• Transmitting discrete I/O status, analog I/O values and modules’ information on hardware commissioning, hardware errors, data errors and signal source node errors.
• Supplying word data transmitted from another devices to local output modules. The R3-NFL1 operation when this device exits the FL-net is selectable: Hold output, Clear output, Switch to the sub system’s control.
• Allotting the cyclic transmission output data of multiple devices bit by bit to local output modules.
■
MESSAGE TRANSMISSION
The module supports the FL-net defined functions listed in the following table. Only the server function is supported.
Server function allows the module to build a response frame to a request message.
Client function allows the module to transmit a request message and to receive its response frame.
PC REQUIREMENTS (provided by the user)
The following PC environment is required to run the R3-NFLBLD program.
Operating system
: Windows 7 (32-bit/64-bit) or Windows 10 (32-bit/64-bit)
Screen area
: 1024 by 768 pixels
LAN card
: Required to connect to Ethernet
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
MODULE STATUS, MODULE ERROR, DATA ERROR, SOURCE NODE ERROR
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)