ES-8428 Rev.11

R3-NL2

Remote I/O R3 Series

LonWorks INTERFACE MODULE

(I/O 56 points)

MODEL: R3–NL2–[1][2]

ORDERING INFORMATION

• Code number: R3-NL2-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-NL2-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] POWER INPUT

N: No power supply
AC Power
K3: 100 – 120 V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
L3: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules.

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• XIF File (Device Interface File)
XIF file is used to define a LonWorks device when programmed on LonMaker.

GENERAL SPECIFICATIONS

Connection
 LonWorks
: Euro type connector terminal
 (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
 Internal bus: Via the Installation Base 
 (model: R3-BSx)
 Internal power: Via the Installation Base (model: R3-BSx) 
 Power input, RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: LonWorks to internal bus or internal power to power input to RUN contact output to FG
Input error data setting: Input value setting at input module error with side DIP SW
Data allocation setting: Set with the side DIP switch
RUN indicator: Bi-color (green/red) LED; Green ON in communications with another device online or changing the output data
(turns off after 25 seconds of no communication)
ERR indicator: Bi-color (green/red) LED; Green ON in normal status; Green blinks when
the APB file is not adequately imported;
Green/Orange turn ON in turn in an abnormality.
RUN CONTACT OUTPUT
RUN contact: Turns on while the green RUN LED is ON (LonWorks in normal communication)
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.

LonWorks COMMUNICATION

Neuron Chip: FT3120 (NeuronID printed in numbers and bar code [peel-off code 39 format])
Transceiver: FT-X1 (equivalent to FTT10A)
Transmission speed: 78 kbps
Twisted-pair cable
Distance, free topology: 500 meters
Max. 64 nodes/channel
LNS: Ver. 3.0 Service Pack 8 or higher
ONLINE indicator: Red LED
ON: Off-line or no network information (decommissioned)
Blinking in approx. 0.5 Hz: On-line
(ready to communicate network variables)
Blinking in approx. 5 Hz for 12 sec.:
Wink message received
SERVICE indicator: Green LED
OFF: Normal operations
Blinking in approx. 0.5 Hz: No network information
ON: Internal program error
SERVICE switch: Used to identify the node in LonWorks
network configuration
RESET switch: Resetting the Neuron Chip

INSTALLATION

Power consumption
AC: Approx. 20 VA
DC: Approx. 12 W
Current consumption (no power supply): 100 mA
Output current (power supply): 250 mA continuous at 20 V DC; 400 mA for 10 minutes
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (LonWorks or internal bus or internal power to power input to RUN contact output to FG)

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TRANSMISSION DATA DESCRIPTIONS

I/O COMBINATIONS

A dedicated Device File for each I/O device depending upon I/O combinations is required for the setting up using an integration tool such as Lon Maker.
On-line download is available for Device Image files at our homepage.
Functional Blocks usable for respective files are not identical to all. Refer to the table below.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Caution: FG terminal is NOT a protective conductor terminal.