ES-8418 Rev.16
R3-NP1
Remote I/O R3 Series
PROFIBUS-DP INTERFACE MODULE
MODEL: R3-NP1-[1][2]
ORDERING INFORMATION
• Code number: R3-NP1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NP1-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
N:
No power supply
AC Power
K3
: 100 – 120 V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
(CE not available)
L3
: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
(CE not available)
DC Power
R:
24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or network modules with the internal power input options.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
■ Mounting on 2-slot base
Use a dedicated base (R3-BS02P) for R3-NP1.
GENERAL SPECIFICATIONS
Connection
PROFIBUS
: 9-pin D-sub connector, female
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal
power
: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: PROFIBUS to internal bus or internal power to power supply to RUN contact output to FG
Input error data setting
: Input value setting at input module error with side DIP SW
Dual communication setting
: Set with the side DIP switch
RUN indicator
: Bi-color (green/Amber) LED
(Function selected with DIP SW)
ERR indicator
: Bi-color (green/red) LED
(Function selected with DIP SW)
■
RUN CONTACT OUTPUT
RUN contact
: Turns ON while the green RUN LED is ON. (PROFIBUS in normal communication)
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA or 150 W
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
PROFIBUS COMMUNICATION
Interface
: PROFIBUS-DP, slave (RS-485 isolation)
Max. baud rate
: 12 Mbps
Protocol
: DPV1
Station No. setting
: Rotary switch; 00 - 7D
(Address is 7D even setting greater value)
GSD file
: Msys093F.GSD
GSD files are downloadable at our web site or at PROFIBUS International site (
www.profibus.com
).
Input data
: Max. 240 bytes
Output data
: Max. 240 bytes
Total I/O data
: Max. 480 bytes
Diagnostics
: Module-related, Status (devicerelated),
Channel-related (max. 32 channels, maskable)
Acyclic communication (MSAC2)
: 2 channels
INSTALLATION
Power consumption
•
AC
:
Approx. 20 VA
•
DC
: Approx. 12 W
Current consumption (no power supply):
130 mA
Output current (power supply)
: 220 mA continuous at 20 V DC; 370 mA for 10 minutes
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (PROFIBUS to internal bus or internal power to power input to RUN output to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.