ES-8399 Rev.9
R3-PA4
Remote I/O R3 Series
HIGH SPEED PULSE INPUT MODULE
(4 points, isolated)
MODEL: R3–PA4[1][2]
ORDERING INFORMATION
• Code number: R3-PA4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-PA4W/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
4
: 4
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8399)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Input 1 to input 2 to input 3 to input 4 to internal bus or internal power
Input range & gain
: Selectable with the side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with input abnormality;
Green in normal operating conditions.
Low-end cutout
: 0.1 %
INPUT SPECIFICATIONS
■
Sensor Excitation
Voltage
: 12 V DC ±10 %
Current
: 15 mA
Current limiting circuit
: Approx. 30 mA
■
INPUT RANGE
: 0 – 100 kHz, 0 – 10 kHz, 0 – 1 kHz, 0 – 100 Hz, 0 – 10 Hz, 0 – 1 Hz, 0 – 0.1 Hz
Minimum pulse width requirement
: 5 μsec. for both ON and OFF
■
DETECTING LEVEL
Detecting level
: 15 – 100 %
(of operational voltage range across the terminals)
Factory setting
: 50 % (programmable using the R3CON PC Configurator software)
Note 1. Each channel has three sets of input terminals.
Input terminal 1: 2 – 5, 7 – 10, 12 – 15, 17 – 20
Input terminal 2: 3 – 5, 8 – 10, 13 – 15, 18 – 20
Input terminal 3: 4 – 5, 9 – 10, 14 – 15, 19 – 20
Note 2. Gain 1 or Gain 2 selectable with the side DIP SW.
Note 3. Measured as 0 % below 15 % of the range.
■
Open Collector
(input terminal 3, gain 1)
Sensor excitation
: 12 V DC
Pull-up resistance
: 20 kΩ (shorted across 1 – 3, 6 – 8, 11 – 13, 16 – 18 respectively)
ON voltage
: ≤ 1.5 V (≤ 2 kΩ recommended)
OFF voltage
: ≥ 2.5 V (≥ 20 kΩ recommended)
(Set detecting level 50 % when the saturation voltage is not greater than 0.8 V, set 70 % when the saturation voltage is between 0.8 to 1.5 V.)
■
Voltage Pulse
(input terminals 1 and 2)
Waveform
: Square, sine or similar waveforms
Input impedance
: 100 kΩ minimum at input terminal 1
20 kΩ minimum at input terminal 2
Operational voltage across the terminals
:
0 – 50 V (input terminal 1, gain 1)
0 – 25 V (input terminal 1, gain 2)
0 – 12 V (input terminal 2, gain 1)
0 – 6 V (input terminal 2, gain 2)
Threshold
: Pulse logic is detected by comparing input pulse voltage and the detecting level. Detecting ‘Rise’ or ‘Sink’ can be switched by using the R3CON PC Configurator software; factory setting ‘Rise’)
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the input range
Data allocation
: 4
Current consumption
:
80 mA (with no load at the sensor excitation)
130 mA (15 mA at each excitation)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM