ES-8390 Rev.7
R3-PD16B
Remote I/O R3 Series
ONE-SHOT PULSE OUTPUT MODULE
(triac output, 16 points)
MODEL: R3-PD16B[1][2]
ORDERING INFORMATION
• Code number: R3-PD16B[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-PD16BW/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
16
: 16
OUTPUT
B
: Triac
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8395)
CAUTION
The output triac may burn out if the load is shortcircuited during operation. Install a fuse at each output terminal.
RELATED PRODUCTS
• Interface module (model: R3-Nx)
Output completion status is compatible with interface modules model: R3-NC1, -NC3, -NE1, -NM1 and -NDx of firmware version V2.00 or higher. Other interface modules are not compatible. So, set I/O Mode as output (SW2-7: ON) to use it.
Note: R3-NL1 and R3-NL2 are not available with this model.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Output
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Output to internal bus or internal power
Output mode setting
: One-Shot Output Mode, ON/OFF Control Output Mode, Continuance Output Mode selectable with DIP switch
Output data length
: 16bit, 8bit selectable with DIP switch
(For ON/OFF Control Output Mode only)
I/O mode setting
: Output Complete Status ON/OFF is selectable with DIP switch
One-shot ON time setting
: 0.1 to 25.6 sec. selectable with DIP switch
ON/OFF control output setting
: Swappable its pair with DIP switch.
Output hold function
: Setting for communication error with side DIP SW (available in continuance output mode)
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/ green) LED;
Green in normal operating conditions;
Red with abnormal configuration.
Output status indicator
: Red LED; turns on with the output ON.
OUTPUT SPECIFICATIONS
Output
: Triac, 16 points
Isolation
: Optical isolator
Common
: All 16 points (4 terminals)
Common current
: Max. 3.2 A per common
Rated load voltage
: 100 – 240 V AC
Operational load voltage
: 85 – 264 V AC
Maximum load current
: 0.4 A per point
Maximum rush current
: 6 A for 1 cycle or less time
Maximum leak current at OFF
: ≤ 1.5 mA
(200 V AC , 60 Hz)
Maximum voltage drop at ON
: ≤ 1.6 V RMS
Other features
: Zero-cross function
No CR absorber and fuse are provided
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Output ON time accuracy
:
±10 % for 1 sec. or less setting;
±0.1 sec. for 1 sec. or more setting
Data allocation
: 1
Current consumption
: 140 mA
Response time
: ≤ 0.1 sec. (delay)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
FUNCTIONS
■
OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
•
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
•
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.
EXTERNAL VIEW
I/O DATA DESCRIPTIONS
DATA ASSIGNMENT
■ Do DATA
■ Di DATA
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM