ES-8931 Rev.4

R3S-DA16

Remote I/O R3 Series

DISCRETE INPUT MODULE

(Di 16 points; with excitation supply, tension clamp terminal block)

MODEL: R3S-DA16[1][2]

ORDERING INFORMATION

• Code number: R3S-DA16[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3S-DA16W/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

16: 16

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS

blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Input: Separable tension clamp terminal  (applicable wire
  size: 0.2 to 1.5 mm2, stripped length 10 mm)
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Input to internal bus or internal power
Excitation monitor: Selectable with side DIP switch; ON/OFF setting available
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator: Red LED; turns on with the input ON.
Read rate: 1 / 5 / 10 / 20 / 50 / 70 / 100 / 200 msec. selectable with DIP SW

INPUT SPECIFICATIONS

Number of input: 16 points
Isolation: Optical isolator, transformer (internal power supply)
Input resistance: Approx. 5.9 kΩ
Common: Negative common per 16 points (20 terminals)
Sensing: 13 V DC
ON current/resistance: ≥ 1.5 mA (≤ 1.5 kΩ)
OFF current/resistance: ≤ 0.75 mA (≥ 18 kΩ)
Detection levels
 ON
: ≥ 10 V
 OFF: ≤ 4 V

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation: 1
Current consumption: 100 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

FUNCTIONS

EXCITATION MONITOR
Enabled/disabled with DIP switch setting.
Excitation Monitor ON
The input is held at the last status when the loss of excitation is detected.
Excitation Monitor OFF
All input signals are turned off when the loss of excitation is detected.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT TERMINAL ASSIGNMENT