ES-8931 Rev.4
R3S-DA16
Remote I/O R3 Series
DISCRETE INPUT MODULE
(Di 16 points; with excitation supply, tension clamp terminal block)
MODEL: R3S-DA16[1][2]
ORDERING INFORMATION
• Code number: R3S-DA16[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-DA16W/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
16
: 16
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: Separable tension clamp terminal (applicable wire
size: 0.2 to 1.5 mm
2
, stripped length 10 mm)
Internal p
ower
: Via the Installation Base (model: R3-BSx)
Isolation
: Input to internal bus or internal power
Excitation monitor
: Selectable with side DIP switch; ON/OFF setting available
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator
: Red LED; turns on with the input ON.
Read rate
: 1 / 5 / 10 / 20 / 50 / 70 / 100 / 200 msec. selectable with DIP SW
INPUT SPECIFICATIONS
Number of input
: 16 points
Isolation
: Optical isolator, transformer (internal power supply)
Input resistance
: Approx. 5.9 kΩ
Common
: Negative common per 16 points (20 terminals)
Sensing
: 13 V DC
ON current/resistance
: ≥ 1.5 mA (≤ 1.5 kΩ)
OFF current/resistance
: ≤ 0.75 mA (≥ 18 kΩ)
Detection levels
ON
: ≥ 10 V
OFF
: ≤ 4 V
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
: 1
Current consumption
: 100 mA
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
FUNCTIONS
■
EXCITATION MONITOR
Enabled/disabled with DIP switch setting.
•
Excitation Monitor ON
The input is held at the last status when the loss of excitation is detected.
•
Excitation Monitor OFF
All input signals are turned off when the loss of excitation is detected.
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
INPUT TERMINAL ASSIGNMENT