ES-8941 Rev.4
R3S-DC8
Remote I/O R3 Series
DISCRETE OUTPUT MODULE
(Do 8 points (relay), tension clamp terminal block)
MODEL: R3S–DC8[1][2]
ORDERING INFORMATION
• Code number: R3S-DC8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-DC8W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
8
: 8
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Output
: Separable tension clamp terminal (applicable wire size: 0.2 to 1.5 mm
2
, stripped length 10 mm)
Internal
power
: Via the Installation Base (model: R3-BSx)
Isolation
: Output 1 to output 2 to output 3 to output 4 to output 5 to output 6 to output 7 to output 8 to internal bus or internal power
Output hold setting
: Setting for communication error with side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Green LED turns on in normal operating conditions.
Output status indicator
:
1 to 8: Red LED; turns on with the output ON.
9 to 16: Unused
OUTPUT SPECIFICATIONS
Output
: Relay contact, 8 points
Common
: 1 point 1 common (8 terminals)
Maximum load current
: 2.0 A per point
Relay driving power
: 24 V DC ±10 %, ≥ 60 mA
Maximum outputs applicable at once
: No limit (at 24 V DC)
Contact rating
: 250 V AC @ 2 A (cos ø = 1)
30 V DC @ 2 A (resistive load)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 500 VA or 60 W
Minimum load
: 5 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycle/min.)
When driving an inductive load, external protection is recommended.
ON delay
: ≤ 10 msec.
OFF delay
: ≤ 10 msec.
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 190 g (0.42 lb)
PERFORMANCE
Data allocation
: 1
Current consumption
: Approx. 60 mA
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output 1 to output 2 to output 3 to output 4 to output 5 to output 6 to output 7 to output 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG;
isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (output)
Pollution Degree 2
Output to internal bus or internal power: Basic insulation
(250 V)
RoHS Directive
FUNCTIONS
■
OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
•
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
•
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
OUTPUT TERMINAL ASSIGNMENT