ES-8938 Rev.5
R3S-SS8N
Remote I/O R3 Series
DC CURRENT INPUT MODULE
(8 points, non-isolated, tension clamp terminal block)
MODEL: R3S-SS8N[1][2]
ORDERING INFORMATION
• Code number: R3S-SS8N[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-SS8NW/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
8
: 8
ISOLATION
N
: Non-isolated between inputs
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8406)
CAUTION
■
UNUSED INPUT CHANNELS
Set the unused channels to “Unused” with PC Configurator software: R3CON. Unused channels left open may be equal to the input lower than -15%, which sets a data abnormality at the PLC or the host device.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: Separable tension clamp terminal (applicable wire size: 0.2 to 1.5 mm
2
, stripped length 10 mm)
Internal power
: Via the Installation Base (model: R3-BSx)
Isolation
: Input 1 or input 2 or input 3 or input 4 or input 5 or input 6 or input 7 or input 8 to internal bus or internal power
Conversion rate
: Selectable with the side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response failure);
Green in normal operating conditions.
INPUT SPECIFICATIONS
■
DC Current
: 4 – 20 mA DC
Input resistance
: 250 Ω resistor incorporated
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy
: Refer to the table at the end of this section.
Conversion rate
: 160 / 80 / 40 / 20 msec. selectable
Data range
: 0 – 10000
Data allocation
: 8
Current consumption
: 60 mA
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Response time
: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input 1 or input 2 or input 3 or input 4 or input 5 or input 6 or input 7 or input 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
INPUT TERMINAL ASSIGNMENT