ES-8969 Rev.2
R3Y-DA16B
Remote I/O R3 Series
AC CONTACT INPUT MODULE
(Di 16 points)
MODEL: R3Y–DA16B[1][2]
ORDERING INFORMATION
• Code number: R3Y-DA16B[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3Y-DA16BW/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
16
: 16 (AC contact input)
INPUT
B
: AC CONTACT INPUT
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: 40-pin connector (OTAX N365P040AU
Fujitsu FCN-365P040-AU...discontinued))
Internal p
ower
: Via the Installation Base (model: R3-BSx)
Isolation
: Input to internal power
Excitation monitor
: Selectable with side DIP switch; ON/OFF setting available
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator
: Red LED; turns on with the input ON.
Read rate
: 1 / 5 / 10 / 20 / 50 / 70 / 100 / 200 msec. selectable with DIP SW
INPUT SPECIFICATIONS
Number of input
: 16 points
Input voltage
: 100 – 132 V AC
Input resistance
: 12 kΩ (60 Hz), 15 kΩ (50 Hz)
Common
: All points (2 terminals)
ON voltage/current
: ≥ 80 V AC, ≥ 5 mA
OFF voltage/current
: ≤ 30 V AC, ≤ 1.7 mA
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
: 1
Current consumption
: 80 mA
Response time
: ≤ 0.1 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(input to internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
FUNCTIONS
•
Excitation Monitor Active
The input is held at the last status when the loss of excitation is detected. The excitation must be connected across CHK (4A/4B or 3A/3B) and COM (2A/2B or 1A/1B).
•
Excitation Monitor Inactive
All input signals are turned off when the loss of excitation is detected.
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
INPUT CONNECTOR (40-pin)