ES-8967 Rev.6
R3Y-SS16N
Remote I/O R3 Series
DC CURRENT INPUT MODULE
(16 points, non-isolated, connector type)
MODEL: R3Y–SS16N[1][2]
ORDERING INFORMATION
• Code number: R3Y-SS16N[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3Y-SS16NW/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
16
: 16
ISOLATION
N
: Non-isolated between inputs
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8405)
CAUTION
■
UNUSED INPUT CHANNELS
Set the unused channels to -20 – +20 mA or 0 – 20 mA range. Otherwise, set them as “Unused” with PC Configurator software: R3CON. Unused channels left open with 4 – 20 mA setting are equal to the input lower than -15 %, which sets a data abnormality at the PLC or the host device.
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Input
: 40-pin connector (OTAX N365P040AU
Fujitsu FCN-365P040-AU...discontinued))
Internal p
ower
: Via the Installation Base (model: R3-BSx)
Isolation
: Input to internal bus or internal power
Input range
: Selectable with the side DIP SW (per 8 channels)
Conversion rate
: Selectable with the side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response failure);
Green in normal operating conditions.
INPUT SPECIFICATIONS
Input
: -20 – +20 mA, 0 – 20 mA, 4 – 20 mA DC
Input resistance
: 75 Ω resistor incorporated
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 160 g (0.35 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Conversion rate
: 100 / 50 / 20 / 10 msec. selectable
Data range
: 0 – 10000 of the input range
Data allocation
: 16
Current consumption
: 100 mA
Temp. coefficient
: ±0.03 %/°C (±0.02 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
INPUT CONNECTOR (40-pin)