ES-8372 Rev.14
R3-YV4
Remote I/O R3 Series
DC VOLTAGE OUTPUT MODULE
(4 points, isolated)
MODEL: R3-YV4[1][2]
ORDERING INFORMATION
• Code number: R3-YV4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-YV4W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
4
: 4
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8372)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Output
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Output 1 to output 2 to output 3 to output 4 to internal bus or internal power
Output range
: Selectable with the side DIP SW
Output hold function
: Setting for communication error with side DIP SW
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Green LED turns on in normal operating conditions.
OUTPUT SPECIFICATIONS
■
Narrow Span
: -1 – +1 V, 0 – 1 V DC
Load resistance
: 10 kΩ min.
■
Wide Span
: -10 – +10 V, -5 – +5 V, 0 – 10 V, 0 – 5 V, 1 – 5 V DC
Load resistance
: 10 kΩ min.
■
Output Range
Except -10 to +10 V DC
: -15 to +115 % of output range
-10 to +10 V DC
: Approx. -11.5 to +11.5 V DC
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy (Range)
:
-10 – +10 V : ±0.05 %
-5 – +5 V : ±0.05 %
-1 – +1 V : ±0.05 %
0 – 10 V : ±0.05 %
0 – 5 V : ±0.1 %
1 – 5 V : ±0.1 %
0 – 1 V : ±0.1 %
Data range
: 0 – 10000 of the output range
Data allocation
: 4
Current consumption
: 150 mA
Temp. coefficient
: ±0.015 % /°C (±0.008 %/°F)
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)
Response time
: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 1 to output 2 to output 3 to output 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A. When an error is detected, the output is switched to the data from the bus B.
•
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
•
Output OFF
If both are in error, the module outputs -15 % (or approx.
-11.5 V) and stands by until one of the communications recovers.
At the startup, it outputs -15 % (or approx. -11.5 V) until the communication is established and normal data is received.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM