ES-6106 Rev.16
R5-BS
Remote I/O R5 Series
INSTALLATION BASE
MODEL: R5–BS[1][2]
ORDERING INFORMATION
• Code number: R5-BS[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R5-BS16/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] I/O CAPACITY
04
: 4 slots
05
: 5 slots (single communication mode)
08
: 8 slots
09
: 9 slots (single communication mode)
16
: 16 slots
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
Only solder side of the main PWB is coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Capacity
Power
: 1 module; 2 modules with Extender Base for Power Supply Module (Model: R5-EX1)
Network interface
: 2 modules
(Only one [1] network module for R5-BS05 and BS09;
Select R5-BS04, BS08 or BS16 for dual-redundant
network communications.)
I/O
:
R5-BS04: 4 modules
R5-BS05: 5 modules
R5-BS08: 8 modules
R5-BS09: 9 modules
R5-BS16: 16 modules
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail
Weight
(No remote I/O module mounted)
R5-BS04, BS05
: 120 g (0.26 lb)
R5-BS08, BS09
: 170 g (0.37 lb)
R5-BS16
: 280 g (0.62 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
(internal power or internal bus to ground)
Dielectric strength
: 2000 V AC @ 1 minute
(internal power or internal bus to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
CURRENT CONSUMPTION
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
■R5-BS04, BS05
■R5-BS08, BS09
■R5-BS16
MOUNTING REQUIREMENTS unit: mm [inch]
■R5-BS04, BS05
■R5-BS08, BS09
■R5-BS16