ES-6126 Rev.11
R5-DC4
Remote I/O R5 Series
DISCRETE OUTPUT MODULE
(relay contact output, 4 points)
MODEL: R5–DC4[1][2]
ORDERING INFORMATION
• Code number: R5-DC4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R5-DC4W/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
4
: 4-point outputs
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R5-BS)
Output
: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
Internal power
: Via the base (model: R5-BS)
Isolation
: Do1 or Do2 to Do3 or Do4 to internal bus or internal power
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
Output status indicator
: Red LED; turns on with the outputs ON.
OUTPUT SPECIFICATIONS
Output
: Relay contact, 4 points
Common
: Every 2 points
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA or 150 W
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Data allocation
: 1
Response time
: ≤ 0.1 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (Do 1 or Do 2 to Do 3 or Do 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (output)
Pollution Degree 2
Output to internal bus or internal power – Basic insulation (300 V)
RoHS Directive
FUNCTIONS
Output hold function
:
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
If both are in error, the module holds the signal and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM