ES-6133 Rev.8
R5-NP2
Remote I/O R5 Series
PROFIBUS-DP INTERFACE MODULE
(for 32-point analog signals)
MODEL: R5-NP2[1]
ORDERING INFORMATION
• Code number: R5-NP2[1]
Specify a code from below for [1].
(e.g. R5-NP2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R5CON)
• GSD (General Station Description) file
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
PROFIBUS
: 9-pin D-sub connector, female
(Lock screw No. 4-40 UNC)
Internal bus
: Via the Installation Base (model: R5-BS)
Internal power
: Via the base (model: R5-BS)
Isolation
: PROFIBUS to internal bus or internal power
RUN indicator
: Bi-color (green/red) LED (refer to the instruction manual)
ERR indicator
: Bi-color (green/red) LED (refer to the instruction manual)
Data allocation
: Fixed to Mode 2
PROFIBUS COMMUNICATION
Interface
: PROFIBUS-DP, slave (RS-485 isolation)
Max. baud rate
: 12 Mbps
Transmission cable
: Approved for PROFIBUS-DP
Station address setting
: Rotary switch; 00 - 7D
(The station address is programmed to 7D if a larger number is set on the switches.)
•Special Clear Mode (Fail Safe Mode) is not supported. However, when the R5-NP2 is initialized
(when the power is turned on), the output of connected output modules is cleared by value “0”: the discrete outputs are turned off; the analog outputs are reset to 0 %.
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (PROFIBUS to internal bus or internal power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ANALOG 16 BITS DATA
■ 16-POINT DISCRETE DATA
■ 4-POINT DISCRETE DATA
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM