ES-6110 Rev.15
R5-PS
Remote I/O R5 Series
POWER SUPPLY MODULE
MODEL: R5–PS[1][2]
ORDERING INFORMATION
• Code number: R5-PS[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R5-PSR/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] POWER INPUT
AC Power
K
: 100 – 120 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L
: 200 – 240 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
NOTICE
■ RUN CONTACT OUTPUT
• Function of RUN contact output
During a Network Module communicates normally with a master device (PLD or PC etc.), RUN contact output of Power Supply Module turns ON.
• When using with dual redundant communication or two system.
During both Network Module or one of them communicates normally with a master device (PLD or PC etc.), RUN contact output of Power Supply Module turns ON.
• When using R5-PS with redundant or two system.
RUN contact output works in same function for both cases. However, when I/O capacity code of installation base is "05:5 slots (single communication mode)" or "09: 9 slots (single communication mode)", the RUN contact output of Power Supply Module installed in a Extender Power Module Base (model: R5-EX1) is not available.
GENERAL SPECIFICATIONS
Connection
•
Power input or RUN contact output
: M3.5 screw terminals
(torque 0.8 N·m)
•
Internal bus or i
nternal power
: Via the Installation Base (model: R5-BS)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Isolation
: Internal bus or internal power to power supply to RUN contact output to FG
Power LED
: Bi-color (red/amber) LED;
Red when the power is supplied; Amber at RUN contact output ON.
■
RUN CONTACT OUTPUT
Contact turns ON (closed) while data from the host is normally received; OFF (open) with loss of communication for approx. 3 seconds.
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage:
250 V AC or 30 V DC
Maximum switching power:
250 VA or 150 W
Minimum load:
1 V DC @ 1 mA
Mechanical life:
2 × 10
7
cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
INSTALLATION
Power consumption
•
AC
: Approx. 90 VA
•
DC
: Approx. 45 W or 1.8 A
Output current
: 1.5 A continuous at 21 V DC;
(Total current continuously consumed at the network modules and I/O modules must be within 1.5 A.)
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS) or Extender Power Supply Module Base (R5-EX1)
Weight
: 250 g (0.55 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (Internal bus or internal power to power input to RUN output to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (RUN contact output)
Installation Category II (power input)
Pollution Degree 2
Internal power or RUN contact output to power input to FG:
Reinforced insulation (300 V)
Internal power to RUN contact output: Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM