ES-7558 Rev.11
R5-RS1A
Remote I/O R5 Series
RTD INPUT MODULE
(re-transmitted output)
MODEL: R5–RS1A[1][2]
ORDERING INFORMATION
• Code number: R5-RS1A[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R5-RS1AW/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
1
: 1 channel
OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 600 Ω max.)
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R5-BS)
I/O
: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
Internal power
: Via the base (model: R5-BS)
Isolation
: Input to output to internal bus or internal power
Zero/Span adj. mode selector
: Rotary switch; monitor mode, adj. mode and simulated output mode selectable
Sensor type
: Selectable with the side DIP SW
Temperature unit
: °C, °F or absolute temperature selectable with the side DIP SW
Burnout detection:
Upscale or downscale selectable with the side DIP SW
Linearization
: Standard
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
INPUT SPECIFICATIONS
Maximum leadwire resistance
:
200 Ω per wire (3-wire)
Sensing current
: ≤
1 mA
OUTPUT SPECIFICATIONS
Operational range
: Approx. 0 – 24 mA DC
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Conversion accuracy
Input
: ±0.4°C (±3.0°C for Cu 10)
Output
: ±0.1% of the retransmitted range + input conversion accuracy
(May exceed ±0.1 % depending upon the input temperature range.)
Conversion data
: Temperature data scaled and converted into 0 – 100 % data and supplied to the internal network bus
Data allocation
: 1
Temp. coefficient
Input
: ±0.015 %/°C (±0.008 %/°F)
Output
: ±0.02 %/°C (±0.01 %/°F)
Response time
: ≤ 0.4 sec. (0 – 90 %)
Burnout response time:
≤ 2 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input to output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
• Zero/Span Adjustment Modes
Monitor Mode
Re-transmits the input signal as output in proportion.
Output 0 % Adjustment Mode
Adjusts the 0 % output signal using the front UP/DOWN buttons, in monitoring the output value with a multimeter. SW1 through SW3 switch the internal increments by 1, 5 and 10.
Output 100 % Adjustment Mode
Adjusts the 100 % output signal using the front UP/DOWN buttons, in monitoring the output value with a multimeter. SW4 through SW6 switch the internal increments by 1, 5 and 10.
Simulated Output Mode
Outputs the simulated signals of 0 %, 50 % and 100 %.
• How to Operate
1) Start up in Monitor Mode (SW position = 0) and wait for 2 or 3 seconds.
2) Switch to another mode and go through the adjustments.
3) Reset the switch to the position ‘0’ so that the new setting is stored in the internal memory.
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM