ES-7781-AG Rev.3

R6D-DA4

Remote I/O R6 Series

DISCRETE INPUT MODULE, 4 points

(Euro terminal)
Functions & Features
• Discrete input module (positive or negative common) with 4 channels

MODEL: R6D–DA4[1]

ORDERING INFORMATION

• Code number: R6D-DA4[1]
Specify a code from below for [1].
  (e.g. R6D-DA4/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC configurator software (model: R6CON)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6D-BS)
 Input: Euro terminal block (torque 0.3 N·m)
 (Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm) 
 Internal power: Via the Installation Base (model: R6D-BS)
Housing material: Flame-resistant resin (black)
Isolation: Input to internal bus or internal power
Module address: Selectable with DIP and rotary switches on the side
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.
Discrete input status indicators: Red LED;
Refer to the instruction manual for details.

INPUT

Common: Positive or negative common (NPN/PNP) per 2 points
Number of I/O: Input, 4 points
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.

INSTALLATION

Current consumption: 10 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6D-BS)
Weight: 60 g (2.1 oz)

PERFORMANCE

Data allocation: 1
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM