ES-7781-AE Rev.2
R6D-YS2
Remote I/O R6 Series
DC CURRENT OUTPUT MODULE
(2 points, Euro terminal)
Functions & Features
• 2 channels for DC current output, compact size remote I/O module
• Output range adjustment with DIP switch or PC configurator
MODEL: R6D–YS2[1]
ORDERING INFORMATION
• Code number: R6D-YS2[1]
Specify a code from below for [1].
(e.g. R6D-YS2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R6CON)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
PACKAGE INCLUDES...
Resistor for unused output terminals (250Ω, 0.25 W)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6D-BS)
Output
: Euro terminal block (torque 0.3 N·m)
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6D-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Output 1 to output 2 to internal bus or internal power
Zero adjustments
: PC programming
Span adjustments
: PC programming
Module address
: Selectable with DIP and rotary switches on the side
Output at the loss of communication
: Selectable with the side DIP SW
Configuration mode
: With DIP switches on the side panel
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
OUTPUT SPECIFICATIONS
Overrange output
: -15 to +115 %
Output range
: 4 – 20 mA DC
Load resistance
: 550 Ω max.
INSTALLATION
Current consumption
: 45 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6D-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
Data allocation
: 2
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F)
Response time
: ≤ 0.25 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 1 to output 2 to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■
OUTPUT HOLD
The output function in case of a loss of communication is selectable with the side DIP SW: Reset the output (to -15 %), Hold the output (last normally received data) or Fix the output at a specific value (PC programming).
The output is held at -15 % of the output range until normal data is received at the startup.
■
OUTPUT WIRE BREAKDOWN DETECTION
In the case of wire breakdown, output error is detected.
Then, the status indicator LED blinks (0.5 seconds per cycle) and the flag of error is set on the PLC etc.
Note: Wire breakdown detection is applicable with Firmware Version 2.00 or later.
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM