ES-7781-AV Rev.3
R6N-PF1
Remote I/O R6 Series
POWER SUPPLY MODULE
(Screw terminal)
Functions & Features
• Provides internal power needed for I/O and network modules from power input
MODEL: R6N–PF1–R[1]
ORDERING INFORMATION
• Code number: R6N-PF1-R[1]
Specify a code from below for [1].
(e.g. R6N-PF1-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6N-BS)
RUN contact output, power supply
: M3 screw terminals (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R6N-BS)
Recommended solderless terminal
: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm
2
Housing material
: Flame-resistant resin (black)
Isolation
: RUN contact output to internal bus or internal power or power input to FG
Power indicator LED
: Green LED turns on when the power is supplied.
RUN indicator
: Orange LED turns on in normal communication with the host PLC.
■
RUN CONTACT OUTPUT
RUN contact
: Terminals (2 – 3) turns ON and (4 – 3) OFF in normal communication with the host PLC;
Terminals (2 – 3) turns OFF and (4 – 3) ON in abnormal communication.
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage:
250 V AC or 30 V DC
Maximum switching power:
250 VA or 150 W
Minimum load:
1 V DC @ 1 mA
Mechanical life:
2 × 10
7
cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
■Recommended solderless terminal (unit: mm [inch])
INSTALLATION
Power input
•
DC
: Operational voltage range 24 V DC ±10 % ripple 10 % p-p max. Approx. 1 A with the maximum I/O extension
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6N-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (RUN contact output to internal bus or internal power or power input to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1,EN 61010-2-201
Measurement Category II (RUN contact output)
Pollution Degree 2
RUN contact output to internal bus or power
supply: Reinforced insulation (300 V)
RoHS Directive
CURRENT CONSUMPTION
The network module and I/O modules operate with 24V DC power supply via the power supply module. The total current consumption of the network module and I/O modules is required to be not more than 1 A. If the total current consumption exceeds 1 A, change the combination of I/O modules or reduce the number of I/O modules.
R6x-SV2 20mA
R6x-SS2 20mA
R6x-TS2 20mA
R6x-TS2A 20mA
R6x-RS2 20mA
R6x-DS1 55mA
R6x-YV2 25mA
R6x-YS2 45mA
R6x-DA4 10mA
R6x-DC4A 20mA
R6x-DC4B 20mA
R6-NC1 110mA
R6-NC3 110mA
R6-ND1 40mA
R6-NE1 75mA
R6-NE2 75mA
R6-NM1 50mA
R6-NM2 50mA
R6-NF1 100mA
R6-NP1 100mA
EXTERNAL VIEW
(With the cover open)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.