ES-7781-BZ Rev.2

R6-PSM

Remote I/O R6 Series

POWER SUPPLY MODULE

Functions & Features
• Provides internal power needed for I/O and network modules from power input
• Universal AC power input

MODEL: R6-PSM

ORDERING INFORMATION

• Code number: R6-PSM[1]
Specify a code from below for [1].
  (e.g. R6-PSM/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT

AC Power
100 – 240 V AC (Operational voltage range 90 – 264 V,
47 – 66 Hz)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• Euro terminal remote I/O R6D series
• Screw terminal remote I/O R6N series
• Tension-clamp remote I/O R6S series

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6x-BS8B)
 RUN contact output, power supply: Euro type connector terminal 
 (Applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) 
 Internal power supply: Via the Installation Base (model: R6x-BS8B)
Housing material: Flame-resistant resin (black)
Isolation: RUN contact output to internal bus or internal power to power supply to FG
Power indicator: Bi-color (green/amber) LED; Green turns ON when the power is supplied. Amber turns ON in normal communication.
RUN CONTACT OUTPUT
RUN contact: ON in normal communication with the host PLC; OFF in communication error.
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.

INSTALLATION

Power input
AC
 Approx. 25 VA at 100 V
 Approx. 30 VA at 200 V
 Approx. 35 VA at 264 V
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: R6x-BS8B)
Weight: 120 g (0.26 lb)

PERFORMANCE

Output (internal power):
24 V ±1 V DC, 400 mA (continuance)
Arrange in order that the total current consumed by the I/O modules or Network modules is within this capacity.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (RUN contact output to internal bus or internal power to power input to FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1,EN 61010-2-201
  Measurement Category II (RUN contact output)
  Installation Category II (power input)
  Pollution Degree 2
  Internal power or RUN contact output to power input to FG:
  Reinforced insulation (300 V)
  Internal power to RUN contact output: Basic insulation (300 V)
RoHS Directive

CURRENT CONSUMPTION

The network module and I/O modules operate with 24V DC power supply via the power supply module.  The total current consumption of the network module and I/O modules is required to be not more than the continuance output current (400mA) of the power supply module.  If the total current consumption exceeds the capacity of the power supply module, change the combination of I/O modules or reduce the number of I/O modules.
R6x-SV2 20mA
R6x-SS2 20mA
R6x-TS2 20mA
R6x-TS2A 20mA
R6x-RS2 20mA
R6x-DS1 55mA
R6x-YV2 25mA
R6x-YS2 45mA
R6x-DA4 10mA
R6x-DC4A 20mA
R6x-DC4B 20mA
R6-NC1 110mA
R6-NC3 110mA
R6-ND1 40mA
R6-NE1 75mA
R6-NE2 75mA
R6-NM1 50mA
R6-NM2 50mA
R6-NF1 100mA
R6-NP1 100mA

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.