ES-8007-F Rev.2
R7F4DD-DAC16C-H
Remote I/O R7F4D Series
DeviceNet® I/O MODULE
(NPN discrete input, NPN discrete output, 8 points each,
e-CON connector)
Functions & Features
• Converts discrete I/O data to the open network fieldbus (DeviceNet)
DeviceNet is registered trademark of ODVA.
MODEL: R7F4DD-DAC16C-H[1]
ORDERING INFORMATION
• Code number: R7F4DD-DAC16C-H[1]
Specify a code from below for [1].
(e.g. R7F4DD-DAC16C-H/Q)
• Specify the specification for option code /Q
(e.g. /C01)
I/O TYPE
DAC16C
: NPN discrete input &
NPN discrete output, 8 points each
TERMINAL BLOCK
H
: Euro type connector terminal for
communication/power supply
e-CON connector for I/O
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• EDS file
The EDS file and configurator software are downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
Communication/power supply, exc. supply
:
Euro type connector terminal
I/O
: e-CON connector
Housing material
: Flame-resistant resin (gray)
Isolation
: Input or exc. supply 1 to output or exc. supply 2 to communication/power supply
Discrete I/O status indicator LED
: Green LED turns on with I/O ON
Configurator connection
: 2.5 dia. miniature jack
DeviceNet COMMUNICATION
Communication/power supply cable
: Approved for DeviceNet
Baud rate setting
: 125 kbps, 250 kbps, 500 kbps, auto-tracking (DIP switch, factory default: auto-tracking)
(Refer to the instruction manual.)
Node address setting
: 0 - 63 (rotary switch, factory default: 00)
(Refer to the instruction manual.)
Status indicator LEDs
: MS, NS
(Refer to the instruction manual for details.)
INPUT SPECIFICATIONS
Common
: Positive common (NPN) per 8 points
Number of inputs
: 8
Maximum inputs applicable at once:
No limit (at 24 V DC)
Sensor excitation
: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 1 A (including discrete input load charge); rated current
8 A
ON voltage / current
: ≥ 17 V DC (X0 through X7 to +24V) / ≥ 2.3 mA
OFF voltage / current
: ≤ 5 V DC (X0 through X7 to +24V) / ≤ 0.75 mA
Input current
: ≤ 3.5 mA per point at 24 V DC
Input resistance
: Approx. 7.2 kΩ
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 0.5 msec.
OUTPUT SPECIFICATIONS
Common
: Negative common (NPN) per 8 points
Number of output
: 8 points
Maximum outputs applicable at once
: No limit (at 24 V DC)
Rated load voltage
: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 1 A (including discrete output load charge); rated current
8 A
Rated output current
: 0.1 A per point, 0.8 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
With shortcircuit protection
With overheat protection
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Supply voltage
: 11 – 25 V DC (supplied from communication/power supply terminal block)
Current consumption
:
Approx. 50 mA @ 24 V DC
Approx. 70 mA @ 11 V DC
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 130 g (0.29 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(input or exc. supply 1 or output or exc. supply 2 to communication/power supply)
500 V AC @ 1 minute
(input or exc. supply 1 to output or exc. supply 2)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■COMMUNICATION/POWER SUPPLY TERMINAL ASSIGNMENT
■EXC. SUPPLY TERMINAL ASSIGNMENT
■I/O TERMINAL ASSIGNMENT
DATA ALLOCATION
I/O DATA DESCRIPTIONS
TRANSMISSION DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM