ES-8009-A Rev.2

R7F4HC-DA32-K

Remote I/O R7F4H Series

CC-Link I/O MODULE

(NPN/PNP discrete input, 32 points, FCN connector)
Functions & Features
• Remote I/O module to input/output digital I/O signal to field bus (CC-Link)

MODEL: R7F4HC-DA32-K-R[1]

ORDERING INFORMATION

• Code number: R7F4HC-DA32-K-R[1]
Specify a code from below for [1].
  (e.g. R7F4HC-DA32-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

I/O TYPE

DA32: NPN/PNP discrete input, 32 points

TERMINAL BLOCK

K: Tension clamp terminal block for power supply
    Tension clamp terminal block for power supply for communicaion
    FCN connector for I/O

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• CSP+ file
The CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.

GENERAL SPECIFICATIONS

Connection
  CC-Link
: Tention clamp terminal block
  Power supply: Tention clamp terminal block
  Input signal, exc. supply: FCN connector
Housing material: Flame-resistant resin (gray)
Isolation: Input to CC-Link to power supply to FE1
Discrete input status indicator LED: Green LED turns on with input ON

CC-Link COMMUNICATION

Transmission: CC-Link Ver.1.10
Network cable: CC-Link cable designated by Mitsubishi Electric
Station Type: Remote I/O device
Data allocation: 1
Station number: 1 - 64 (rotary switch, default:00)
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (DIP switch)
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator LEDs: Power, Run, Error, SD, RD
(For details, refer to the users manual.)

INPUT SPECIFICATIONS

Common: Positive or negative common (NPN/PNP) per 32 points
Number of inputs: 32
Maximum inputs applicable at once: No limit (at 24 V DC)
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 17 V DC (input – COM) / ≥ 2.3 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 0.75 mA
Input current: ≤ 3.5 mA per point at 24 V DC
Input resistance: Approx. 7.2 kΩ
ON delay: ≤ 0.5 msec.
OFF delay: ≤ 0.5 msec.

INSTALLATION

Current consumption
DC (@ 24 V DC): ≤ 40 mA
 (contact I/O load charge is not included)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 160 g (0.35 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to CC-Link to power supply to FE1)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

TERMINAL ASSIGNMENTS

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.