ES-8009-C Rev.2
R7F4HC-DAC32D-K
Remote I/O R7F4H Series
CC-Link I/O MODULE
(NPN/PNP discrete input, PNP discrete output, 16 points each, FCN connector)
Functions & Features
• Remote I/O module to input/output digital I/O signal to field bus (CC-Link)
MODEL: R7F4HC-DAC32D-K-R[1]
ORDERING INFORMATION
• Code number: R7F4HC-DAC32D-K-R[1]
Specify a code from below for [1].
(e.g. R7F4HC-DAC32D-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
I/O TYPE
DAC32D
: NPN/PNP discrete input &
PNP discrete output, 16 points each
TERMINAL BLOCK
K
: Tension clamp terminal block for power supply
Tension clamp terminal block for power supply for communicaion
FCN connector for I/O
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• CSP+ file
The CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
GENERAL SPECIFICATIONS
Connection
CC-Link
: Tention clamp terminal block
Power supply
: Tention clamp terminal block
I/O signal, exc. supply
: FCN connector
Housing material
: Flame-resistant resin (gray)
Isolation
: I/O or exc. supply to CC-Link to power supply to FE1
Discrete I/O status indicator LED
: Green LED turns on with I/O ON
CC-Link COMMUNICATION
Transmission:
CC-Link Ver.1.10
Network cable
: CC-Link cable designated by Mitsubishi Electric
Station Type
: Remote I/O device
Data allocation
: 1
Station number
: 1 - 64 (rotary switch, default:00)
Baud rate setting
: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (DIP switch)
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator LEDs
: Power, Run, Error, SD, RD
(For details, refer to the users manual.)
INPUT SPECIFICATIONS
Common
: Positive or negative common (NPN/PNP) per 16 points
Number of inputs
: 16
Maximum inputs applicable at once
: No limit (at 24 V DC)
Rated input voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 17 V DC (input – COM) / ≥ 2.3 mA
OFF voltage / current
: ≤ 5 V DC (input – COM) / ≤ 0.75 mA
Input current
: ≤ 3.5 mA per point at 24 V DC
Input resistance
: Approx. 7.2 kΩ
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 0.5 msec.
OUTPUT SPECIFICATIONS
Common
: Positive common (PNP) per 16 points
Number of output
: 16 points
Maximum outputs applicable at once
: No limit (at 24 V DC)
Rated load voltage
: 24 V DC ±10 %, ripple 5 %p-p max.
Rated output current
: 0.1 A per point, 1.6 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
With shortcircuit protection
With overheat protection
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Current consumption
•
DC (@ 24 V DC)
: ≤ 50 mA
(contact I/O load charge is not included)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 160 g (0.35 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(I/O or exc. supply to CC-Link to power supply to FE1)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
CONNECTION DIAGRAMS
TERMINAL ASSIGNMENTS
DATA ALLOCATION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.